4.7 PROTECTION TESTS
4 ACCEPTANCE TESTS
4
4.7.8 T11: ANTI-MOTORING 32-2
Skip this test if your DGP model does not include this function. This function is not available
on DGP***ABA model relays.
1.
Settings:
32-2
(903) REV PWR = 1.5 (0.3)
(904) TL2 = 1
DIG INP
(2501) SELBKDI1 = NO BLK (0)
2.
Connect relay as shown in Figure 4–8: STANDARD FUNCTIONAL TEST CONNECTIONS on page 4–26.
3.
Set up relay in test mode for the 32-2 function; 32-2 ON will be displayed on the MMI.
4.
Using a 60 Hz source set the voltage inputs to:
VA = 20 V rms
∠
0°,
VB = 20V rms
∠
–120°,
VC = 20V rms
∠
–240°.
5.
Set the current input to IA = 0.1 (0.02) A rms
∠
180°. Phases B and C should have no current.
6.
Verify that test pickup operates immediately and test trip operates in 1.00 to 1.05 seconds.
4.7.9 T12: TIME OVERCURRENT WITH VOLTAGE RESTRAINT 51V
1.
Settings:
51V
(1003) PICKUP = 0.5 (0.1)
(1004) TIME FAC = 1.0
2.
Connect relay as shown in Figure 4–8: STANDARD FUNCTIONAL TEST CONNECTIONS on page 4–26.
3.
Set up relay in test mode for the 51V function; 51V ON will be displayed on the MMI.
4.
Using a 60 Hz source set the voltage inputs to:
VA = 70V rms
∠
0°
VB = 70V rms
∠
–120°
VC = 70V rms
∠
–240°.
Set the current inputs according to the table below.
Table 4–3: CURRENT INPUTS FOR TEST T12
TEST
PHASE A
PHASE B
PHASE C
MAG.
PHASE
MAG.
PHASE
MAG.
PHASE
A
0.45 (0.09) A
0°
0.45 (0.09) A
–120°
0.45 (0.09) A
–240°
B
2.0 (0.4) A
0°
2.0 (0.4) A
–120°
2.0 (0.4) A
–240°
NOTE
Summary of Contents for DGP Series
Page 2: ......
Page 4: ......
Page 192: ...8 18 DGP Digital Generator Protection System GE Power Management 8 5 PASSWORDS 8 INTERFACE 8...
Page 260: ...B 4 DGP Digital Generator Protection System GE Power Management B 1 CHANGE NOTES APPENDIXB B...
Page 262: ...B 6 DGP Digital Generator Protection System GE Power Management B 1 CHANGE NOTES APPENDIXB B...
Page 268: ...D 2 DGP Digital Generator Protection System GE Power Management D 1 DGP WARRANTY APPENDIXD D...
Page 276: ...viii DGP Digital Generator Protection System GE Power Management INDEX INDEX...
Page 277: ...GE Power Management DGP Digital Generator Protection System NOTES...