DGP Digital Generator Protection System
GE Power Management
6.3 TROUBLESHOOTING
6 SERVICING
6
6.3.5 SERVICING SYSTEM STATUS FAILURES
A system failure is one that indicates a failure of a power system input, or indicates that the relay has been dis-
abled by a user command. They are indicated by the non-critical alarm contacts, by a red LED, or by the critical
alarm contacts. However, no MMI display is provided until the INFORMATION–STATUS command is used.
Turn off then re-apply the DC input power. The non-critical alarm contact (N.O.) will be closed if the failure still
exists. Use the INFORMATION–STATUS to determine the cause of the trouble.
Table 6–4: SYSTEM STATUS ERROR MESSAGES
SYSTEM STATUS ERROR
INDICATION
DESCRIPTION
WARN
NCA
WARN condition, press up arrow
FAIL
CA/LED
FAIL condition, press up arrow
MISC
LED
Miscellaneous condition, press up arrow
Note: LED = red LED on the MMI; NCA = energizing the non-critical alarm relay
CA = de-energizing the critical alarm relay.
Table 6–5: MISCELLANEOUS MESSAGES
MISCELLANEOUS MESSAGES
DESCRIPTION
INDICATION
PROT OFF
Protection off
LED
DIS OUTS
Outputs Disabled
LED
RELAY TEST
Relay in Test Mode
LED
D O TEST
Digital Output test
LED
Summary of Contents for DGP Series
Page 2: ......
Page 4: ......
Page 192: ...8 18 DGP Digital Generator Protection System GE Power Management 8 5 PASSWORDS 8 INTERFACE 8...
Page 260: ...B 4 DGP Digital Generator Protection System GE Power Management B 1 CHANGE NOTES APPENDIXB B...
Page 262: ...B 6 DGP Digital Generator Protection System GE Power Management B 1 CHANGE NOTES APPENDIXB B...
Page 268: ...D 2 DGP Digital Generator Protection System GE Power Management D 1 DGP WARRANTY APPENDIXD D...
Page 276: ...viii DGP Digital Generator Protection System GE Power Management INDEX INDEX...
Page 277: ...GE Power Management DGP Digital Generator Protection System NOTES...