GE Power Management
DGP Digital Generator Protection System
2-
55
2 CALCULATION OF SETTINGS
2.4 COMMISSIONING
2
2103
SET PNT
Set point
Hz
2104
TL15
Timer TL15 setting
Sec.
OVERFREQUENCY SETPOINT 2: 81-2O
2201
TRIP
Configure trip outputs
2202
ALARM
Configure alarm outputs
2203
SET PNT
Set point
Hz
2204
TL16
Timer TL16 setting
Sec.
OVERFREQUENCY SETPOINT 3: 81-3O
2301
TRIP
Configure trip outputs
2302
ALARM
Configure alarm outputs
2303
SET PNT
Set point
Hz
2304
TL17
Timer TL17 setting
Sec.
OVERFREQUENCY SETPOINT 4: 81-4O
2401
TRIP
Configure trip outputs
2402
ALARM
Configure alarm outputs
2403
SET PNT
Set point
Hz
2404
TL18
Timer TL18 setting
Sec.
DIGITAL INPUT: DIG INP
2501
SELBKDI1
Select blocking action by input DI1
2502
DI3 TRIP
Configure trip outputs
2503
DI3 ALRM
Configure alarm outputs
2504
DI3 TIMR
Pickup Delay, DI3 timer
sec.
2505
DI4 TRIP
Configure trip outputs
2506
DI4 ALRM
Configure alarm outputs
2507
DI4 TIMR
Pickup delay, DI4 timer
sec.
2508
DI6 FUNC
Define DI6 Function
VOLTAGE TRANSFORMER FUSE FAILURE: VTFF
2601
VTFF
Enable/Disable VTFF
ACCIDENTAL ENERGIZATION: AE
2701
TRIP
Configure trip outputs
Table 2–7: DGP
***
ACA SETTINGS TABLE (Sheet 5 of 6)
LOCATION: GENERATOR
NUMBER:
RELAY MODEL NUMBER: DGP _ _ _ ACA
PROM VERSION NUMBER: V _ _ _ . _ _ _ _ _ D
SETTING #
MNEMONIC
DESCRIPTION
USER SETTING
Summary of Contents for DGP Series
Page 2: ......
Page 4: ......
Page 192: ...8 18 DGP Digital Generator Protection System GE Power Management 8 5 PASSWORDS 8 INTERFACE 8...
Page 260: ...B 4 DGP Digital Generator Protection System GE Power Management B 1 CHANGE NOTES APPENDIXB B...
Page 262: ...B 6 DGP Digital Generator Protection System GE Power Management B 1 CHANGE NOTES APPENDIXB B...
Page 268: ...D 2 DGP Digital Generator Protection System GE Power Management D 1 DGP WARRANTY APPENDIXD D...
Page 276: ...viii DGP Digital Generator Protection System GE Power Management INDEX INDEX...
Page 277: ...GE Power Management DGP Digital Generator Protection System NOTES...