9-
22
DGP Digital Generator Protection System
GE Power Management
9.5 MODBUS MEMORY MAPPING
9 COMMUNICATIONS
9
bit 2 = POWER SUPPLY 1:
+12 V Failed
bit 3 = POWER SUPPLY 1 & 2:
+12 V Failed
bit 4 = POWER SUPPLY 1:
–12 V Warning
bit 5 = POWER SUPPLY 2:
–12 V Warning
bit 6 = POWER SUPPLY 1:
–12 V Failed
bit 7 = POWER SUPPLY 1 & 2:
–12 V Failed
bit 8-15 = Spare
180Bh:
PWR2STAT:
bit 0 = POWER SUPPLY 1: Warning
bit 1 = POWER SUPPLY 2: Warning
bit 2 = POWER SUPPLY 1: Failed
bit 3 = POWER SUPPLY 1 & 2: Failed
bit 4-15 = Spare
180Ch:
MISCSTAT:
bit 0 = Protection Enabled Flag
bit 1 = Digital Output Enable Flag
bit 2 = Case to Ground Shorted
bit 3 = Spare
bit 4 = Fuse Failure
bit 5 = Logon Failure
bit 6 = Remote Manual-Trip Jumper
Installed
bit 7 = Remote Change-Settings
Jumper Installed
bit 8 = TEST MODE Activated
bit 9 = Time Strobe Failed
bit 10 = Digital Output Test Activated
bit 11 = 94G-A Trip Continuity Error
bit 12 = 94G-B Trip Continuity Error
bit 13 = 94G-C Trip Continuity Error
bit 14 = 94G-D Trip Continuity Error
bit 15 = Spare
REGISTER
BIT ASSIGNMENT
Summary of Contents for DGP Series
Page 2: ......
Page 4: ......
Page 192: ...8 18 DGP Digital Generator Protection System GE Power Management 8 5 PASSWORDS 8 INTERFACE 8...
Page 260: ...B 4 DGP Digital Generator Protection System GE Power Management B 1 CHANGE NOTES APPENDIXB B...
Page 262: ...B 6 DGP Digital Generator Protection System GE Power Management B 1 CHANGE NOTES APPENDIXB B...
Page 268: ...D 2 DGP Digital Generator Protection System GE Power Management D 1 DGP WARRANTY APPENDIXD D...
Page 276: ...viii DGP Digital Generator Protection System GE Power Management INDEX INDEX...
Page 277: ...GE Power Management DGP Digital Generator Protection System NOTES...