2-
4
DGP Digital Generator Protection System
GE Power Management
2.1 GENERAL
2 CALCULATION OF SETTINGS
2
303
TL14
1 to 9
sec.
1
CURRENT UNBALANCE – TRIP: 46T
401
TRIP
0000 to 1111
N/A
0000
402
ALARM
0000 to 1111
N/A
0000
403
PICKUP
0.05 to 2.99
0.01 to 0.60
A
2.00
0.40
404
K2
1.0 to 45.0
sec.
1.0
LOSS OF EXCITATION – SUPERVISION: 40
501
SELV2SUP
DISABLE (0); ENABLE (1)
N/A
DISABLE
LOSS OF EXCITATION – ZONE 1: 40-1
601
TRIP
0000 to 1111
N/A
0000
602
ALARM
0000 to 1111
N/A
0000
603
CENTER
2.50 to 60.00
12.5 to 300.00
Ω
11.00
55.00
604
RADIUS
2.50 to 60.00
12.5 to 300.00
Ω
8.50
42.50
605
TL12
0.01 to 9.99
sec.
0.01
LOSS OF EXCITATION – ZONE 2: 40-2
701
TRIP
0000 to 1111
N/A
0000
702
ALARM
0000 to 1111
N/A
0000
703
CENTER
2.50 to 60.00
12.50 to 300.0
Ω
11.00
55.00
704
RADIUS
2.50 to 60.00
12.50 to 300.0
Ω
8.50
42.50
705
TL13
0.01 to 9.99
sec.
0.01
ANTI-MOTORING #1: 32-1
801
TRIP
0000 to 1111
N/A
0000
802
ALARM
0000 to 1111
N/A
0000
803
SQ TR EN
YES [1/Y]; NO [3/N]
N/A
YES
804
REV PWR
0.5 to 99.9
0.1 to 19.9
W
1.5
0.3
805
TL1
1 to 120
sec.
5
ANTI-MOTORING #2: 32-2
901
d
TRIP
0000 to 1111
N/A
0000
Table 2–1: DGP SYSTEM SETTINGS & RATINGS (Sheet 2 of 7)
SETTING
NUMBER
MNEMONIC
RANGE
DEFAULT
5 AMP
1 AMP
UNITS
5 AMP
1 AMP
c 6HW WR PDWFK WKH V\VWHP SKDVH VHTXHQFH 6HWWLQJ LQIRUPV WKH UHOD\ RI DFWXDO V\VWHP SKDVH VHTXHQFH HLWKHU $%& RU $&% &7
DQG 97 LQSXWV ODEHOHG $ % DQG & RQ WKH '*3 PXVW EH FRQQHFWHG WR V\VWHP SKDVHV $ % DQG & IRU FRUUHFW RSHUDWLRQ
d 6HWWLQJYDOXH QRW DYDLODEOH LQ '*3$%$ PRGHOV
e 6HWWLQJYDOXH QRW DYDLODEOH LQ '*3$$$ PRGHOV
f 6HWWLQJYDOXH QRW DYDLODEOH LQ '*3&$ PRGHOV
.
Summary of Contents for DGP Series
Page 2: ......
Page 4: ......
Page 192: ...8 18 DGP Digital Generator Protection System GE Power Management 8 5 PASSWORDS 8 INTERFACE 8...
Page 260: ...B 4 DGP Digital Generator Protection System GE Power Management B 1 CHANGE NOTES APPENDIXB B...
Page 262: ...B 6 DGP Digital Generator Protection System GE Power Management B 1 CHANGE NOTES APPENDIXB B...
Page 268: ...D 2 DGP Digital Generator Protection System GE Power Management D 1 DGP WARRANTY APPENDIXD D...
Page 276: ...viii DGP Digital Generator Protection System GE Power Management INDEX INDEX...
Page 277: ...GE Power Management DGP Digital Generator Protection System NOTES...