1-
6
DGP Digital Generator Protection System
GE Power Management
1.3 PROTECTION FEATURES
1 PRODUCT DESCRIPTION
1
1.3 PROTECTION FEATURES
1.3.1 DESCRIPTION
The following protection functions are included with the DGP system.
A single-line diagram for the DGP is shown below.
Figure 1–2: SINGLE LINE DIAGRAM
Table 1–3: DGP PROTECTION FUNCTIONS
PROTECTION FUNCTION
ANSI CODE(S)
Stator Differential
87G
Current Unbalance
46
Loss of Excitation
40
Anti-Motoring
32
Time Overcurrent with Voltage Restraint
51V
Stator Ground
64G1, 64G2, 27TN
Ground Overcurrent
51GN
Over-excitation
24
Overvoltage
59
Undervoltage
27
Over and Underfrequency
81
Voltage Transformer Fuse Failure
VTFF
Accidental Energization
AE
To
MODEM
To
LAPTOP
PC
TRIP
ALARM
52G
GSU
Transf.
TO
POWER
SYSTEM
GEN.
51GN
64G1
64G2
27NT
RS232
46
87G
40
32
51V
VTFF
RS232
64G2
24
32
40
27
59
81
VTFF
DGP
51V
Summary of Contents for DGP Series
Page 2: ......
Page 4: ......
Page 192: ...8 18 DGP Digital Generator Protection System GE Power Management 8 5 PASSWORDS 8 INTERFACE 8...
Page 260: ...B 4 DGP Digital Generator Protection System GE Power Management B 1 CHANGE NOTES APPENDIXB B...
Page 262: ...B 6 DGP Digital Generator Protection System GE Power Management B 1 CHANGE NOTES APPENDIXB B...
Page 268: ...D 2 DGP Digital Generator Protection System GE Power Management D 1 DGP WARRANTY APPENDIXD D...
Page 276: ...viii DGP Digital Generator Protection System GE Power Management INDEX INDEX...
Page 277: ...GE Power Management DGP Digital Generator Protection System NOTES...