D30 Line Distance Protection System
GE Multilin
5.2 PRODUCT SETUP
5 SETTINGS
5
The user-programmable pushbutton logic is shown below.
Figure 5–12: USER-PROGRAMMABLE PUSHBUTTON LOGIC (Sheet 1 of 2)
S
R
Non-volatile latch
Latch
OR
OR
OR
OR
OR
OR
AND
SETTING
= Enabled
= Latched
Function
= Self-Reset
SETTING
Off = 0
Remote Lock
SETTING
Off = 0
Local Lock
SETTING
Off = 0
Set
SETTING
Off = 0
Reset
SETTING
= Enabled
= Disabled
Autoreset Function
FLEXLOGIC OPERAND
PUSHBUTTON 1 ON
FLEXLOGIC OPERAND
PUSHBUTTON 1 OFF
TIMER
200 ms
0
AND
AND
AND
AND
AND
TIMER
50 ms
0
TIMER
50 ms
0
SETTING
Autoreset Delay
T
PKP
0
TIMER
200 ms
0
AND
AND
SETTING
Drop-Out Timer
T
RST
0
PUSHBUTTON ON
To user-programmable
pushbuttons logic
sheet 2, 842024A2
LATCHED
LATCHED/SELF-RESET
To user-programmable
pushbuttons logic
sheet 2, 842024A2
842021A3.CDR
SETTING
Hold
T
PKP
0
Summary of Contents for D30D00HCHF8AH6AM6BP8BX7A
Page 10: ...x D30 Line Distance Protection System GE Multilin TABLE OF CONTENTS...
Page 374: ...5 248 D30 Line Distance Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5...
Page 398: ...6 24 D30 Line Distance Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6...
Page 410: ...7 12 D30 Line Distance Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7...
Page 444: ...9 24 D30 Line Distance Protection System GE Multilin 9 5 FAULT LOCATOR 9 THEORY OF OPERATION 9...
Page 576: ...B 102 D30 Line Distance Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B...
Page 616: ...D 10 D30 Line Distance Protection System GE Multilin D 1 IEC 60870 5 104 PROTOCOL APPENDIX D D...
Page 628: ...E 12 D30 Line Distance Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E...
Page 636: ...F 8 D30 Line Distance Protection System GE Multilin F 3 WARRANTY APPENDIX F F...
Page 646: ...x D30 Line Distance Protection System GE Multilin INDEX...