GE Multilin
D30 Line Distance Protection System
B-9
APPENDIX B
B.4 MEMORY MAPPING
B
B.4MEMORY MAPPING
B.4.1 MODBUS MEMORY MAP
The table provides the Modbus memory map. The addresses in the table are expressed in hexadecimal. The particular reg-
isters actually present depend on the UR product and on the order codes software and module options.
The map is also viewable in a web browser. In the browser, enter the IP address of the UR and click the option.
In the table, "Grouped Setting" refers to content in the
Settings > Grouped Elements > Group
menus.
The data format tables that follow the memory map provide more information for some entries.
Table B–10: MODBUS MEMORY MAP (Sheet 1 of 58)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Product Information (Read Only)
0000
UR Product Type
0 to 65535
---
1
F001
0
0002
Product Version
0 to 655.35
---
0.01
F001
1
0003
Boot Configuration Register
0 to 65535
---
1
F001
0
Product Information (Read Only -- Written by Factory)
0010
Serial Number
---
---
---
F203
“0”
0020
Manufacturing Date
0 to 4294967295
---
1
F050
0
0022
Modification Number
0 to 65535
---
1
F001
0
0040
Order Code
---
---
---
F204
“Order Code x”
0090
Ethernet MAC Address
---
---
---
F072
0
0093
Reserved (13 items)
---
---
---
F001
0
00A0
CPU Module Serial Number
---
---
---
F203
(none)
00B0
CPU Supplier Serial Number
---
---
---
F203
(none)
00C0
Ethernet Sub Module Serial Number (8 items)
---
---
---
F203
(none)
Product Information (Read Only -- Written by Factory)
0110
FPGA Version
---
---
---
F206
(none)
0113
FPGA Date
0 to 4294967295
--
1
F050
0
Self Test Targets (Read Only)
0200
Self Test States (4 items)
0 to 4294967295
0
1
F143
0
Front Panel (Read Only)
0208
LED Column
n
State,
n
= 1 to 10 (10 items)
0 to 65535
---
1
F501
0
0220
Display Message
---
---
---
F204
(none)
0248
Last Key Pressed
0 to 47
---
1
F530
0 (None)
Keypress Emulation (Read/Write)
0280
Simulated keypress -- write zero before each keystroke
0 to 46
---
1
F190
0 (No key -- use
between real
keys)
Virtual Input Commands (Read/Write Command) (64 modules)
0400
Virtual Input 1 State
0 to 1
---
1
F108
0 (Off)
0401
Virtual Input 2 State
0 to 1
---
1
F108
0 (Off)
0402
Virtual Input 3 State
0 to 1
---
1
F108
0 (Off)
0403
Virtual Input 4 State
0 to 1
---
1
F108
0 (Off)
0404
Virtual Input 5 State
0 to 1
---
1
F108
0 (Off)
0405
Virtual Input 6 State
0 to 1
---
1
F108
0 (Off)
0406
Virtual Input 7 State
0 to 1
---
1
F108
0 (Off)
0407
Virtual Input 8 State
0 to 1
---
1
F108
0 (Off)
0408
Virtual Input 9 State
0 to 1
---
1
F108
0 (Off)
0409
Virtual Input 10 State
0 to 1
---
1
F108
0 (Off)
040A
Virtual Input 11 State
0 to 1
---
1
F108
0 (Off)
040B
Virtual Input 12 State
0 to 1
---
1
F108
0 (Off)
040C
Virtual Input 13 State
0 to 1
---
1
F108
0 (Off)
040D
Virtual Input 14 State
0 to 1
---
1
F108
0 (Off)
040E
Virtual Input 15 State
0 to 1
---
1
F108
0 (Off)
040F
Virtual Input 16 State
0 to 1
---
1
F108
0 (Off)
0410
Virtual Input 17 State
0 to 1
---
1
F108
0 (Off)
Summary of Contents for D30D00HCHF8AH6AM6BP8BX7A
Page 10: ...x D30 Line Distance Protection System GE Multilin TABLE OF CONTENTS...
Page 374: ...5 248 D30 Line Distance Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5...
Page 398: ...6 24 D30 Line Distance Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6...
Page 410: ...7 12 D30 Line Distance Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7...
Page 444: ...9 24 D30 Line Distance Protection System GE Multilin 9 5 FAULT LOCATOR 9 THEORY OF OPERATION 9...
Page 576: ...B 102 D30 Line Distance Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B...
Page 616: ...D 10 D30 Line Distance Protection System GE Multilin D 1 IEC 60870 5 104 PROTOCOL APPENDIX D D...
Page 628: ...E 12 D30 Line Distance Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E...
Page 636: ...F 8 D30 Line Distance Protection System GE Multilin F 3 WARRANTY APPENDIX F F...
Page 646: ...x D30 Line Distance Protection System GE Multilin INDEX...