6-22
D30 Line Distance Protection System
GE Multilin
6.4 RECORDS
6 ACTUAL VALUES
6
6.4.3 OSCILLOGRAPHY
PATH: ACTUAL VALUES
RECORDS
OSCILLOGRAPHY
This menu allows the user to view the number of triggers involved and number of oscillography traces available. The
CYCLES PER RECORD
value is calculated to account for the fixed amount of data storage for oscillography. See the
Oscillog-
raphy
section of chapter 5 for additional details.
A trigger can be forced here at any time by setting “Yes” to the
FORCE TRIGGER?
command. Refer to the
COMMANDS
CLEAR RECORDS
menu for information on clearing the oscillography records.
6.4.4 BREAKER MAINTENANCE
PATH: ACTUAL VALUES
RECORDS
MAINTENANCE
BREAKER 1(2)
There is an identical menu for each of the breakers. The
BKR 1 ARCING AMP
values are in units of kA
2
-cycles. Refer to the
COMMANDS
CLEAR RECORDS
menu for clearing breaker arcing current records. The
BREAKER OPERATING TIME
is
defined as the slowest operating time of breaker poles that were initiated to open.
OSCILLOGRAPHY
FORCE TRIGGER?
No
Range: No, Yes
MESSAGE
NUMBER OF TRIGGERS:
0
MESSAGE
AVAILABLE RECORDS:
0
MESSAGE
CYCLES PER RECORD:
0.0
MESSAGE
LAST CLEARED DATE:
2000/07/14
15:40:16
BREAKER 1
BKR 1 ARCING AMP
φ
A:
0.00 kA2-cyc
MESSAGE
BKR 1 ARCING AMP
φ
B:
0.00 kA2-cyc
MESSAGE
BKR 1 ARCING AMP
φ
C:
0.00 kA2-cyc
MESSAGE
BKR 1 OPERATING TIME
φ
A: 0
ms
MESSAGE
BKR 1 OPERATING TIME
φ
B: 0
ms
MESSAGE
BKR 1 OPERATING TIME
φ
C: 0
ms
MESSAGE
BKR 1 OPERATING
TIME:
0 ms
Summary of Contents for D30D00HCHF8AH6AM6BP8BX7A
Page 10: ...x D30 Line Distance Protection System GE Multilin TABLE OF CONTENTS...
Page 374: ...5 248 D30 Line Distance Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5...
Page 398: ...6 24 D30 Line Distance Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6...
Page 410: ...7 12 D30 Line Distance Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7...
Page 444: ...9 24 D30 Line Distance Protection System GE Multilin 9 5 FAULT LOCATOR 9 THEORY OF OPERATION 9...
Page 576: ...B 102 D30 Line Distance Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B...
Page 616: ...D 10 D30 Line Distance Protection System GE Multilin D 1 IEC 60870 5 104 PROTOCOL APPENDIX D D...
Page 628: ...E 12 D30 Line Distance Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E...
Page 636: ...F 8 D30 Line Distance Protection System GE Multilin F 3 WARRANTY APPENDIX F F...
Page 646: ...x D30 Line Distance Protection System GE Multilin INDEX...