5-50
D30 Line Distance Protection System
GE Multilin
5.2 PRODUCT SETUP
5 SETTINGS
5
PORT 1 ... 3 PATH DELAY ASYMMETRY
•
This setting corresponds to “delayAsymmetry” in PTP, which is used by the peer delay mechanism to compensate for
any difference in the propagation delay between the two directions of a link. Except in unusual cases, the two fibers are
of essentially identical length and composition, so this setting should be set to zero.
•
In unusual cases where the length of the link is different in different directions, this setting should be set to the number
of nanoseconds the Ethernet propagation delay to the relay is longer than the mean of path propagation delays to and
from the relay. For instance, if it is known say from the physical length of the fibers and the propagation speed in the
fibers that the delay from the relay to the Ethernet switch it is connected to is 9 000 ns and the that the delay from the
switch to the relay is 11 000 ns, then the mean delay is 10 000 ns, and the path delay asymmetry is 11000 - 10000 =
+1000 ns.
c) SNTP PROTOCOL
PATH: SETTINGS
PRODUCT SETUP
REAL TIME CLOCK
SNTP PROTOCOL
The D30 supports the Simple Network Time Protocol specified in RFC-2030. With SNTP, the D30 can obtain clock time
over an Ethernet network. The D30 acts as an SNTP client to receive time values from an SNTP/NTP server, usually a ded-
icated product using a GPS receiver to provide an accurate time. UR series relays support unicast, broadcast, multicast,
and anycast SNTP functionality.
The
SNTP FUNCTION
setting enables or disabled the SNTP feature on the D30.
To use SNTP in unicast mode,
SNTP SERVER IP ADDR
must be set to the SNTP/NTP server IP address. Once this address is
set and
SNTP FUNCTION
is “Enabled,” the D30 attempts to obtain time values from the SNTP/NTP server. Since many time
values are obtained and averaged, it generally takes three to four minutes until the D30 clock is closely synchronized with
the SNTP/NTP server. It takes up to two minutes for the D30 to signal an SNTP self-test error if the server is offline.
To use SNTP in broadcast mode, set the
SNTP SERVER IP ADDR
setting to “0.0.0.0” and
SNTP FUNCTION
to “Enabled.” The
D30 then listens to SNTP messages sent to the “all ones” broadcast address for the subnet. The D30 waits up to 18 min-
utes (>1024 seconds) without receiving an SNTP broadcast message before signaling an SNTP self-test error.
The
SNTP UDP PORT NUMBER
is 123 for normal SNTP operation. If SNTP is not required, close the port by setting it to 0.
When the
SNTP UDP PORT NUMBER
is set to 0, the change takes effect when the D30 is restarted.
SNTP PROTOCOL
SNTP FUNCTION:
Disabled
Range: Enabled, Disabled
MESSAGE
SNTP SERVER IP ADDR:
0.0.0.0
Range: Standard IP address format
MESSAGE
SNTP UDP PORT
NUMBER: 123
Range: 0 to 65535 in steps of 1
NOTE
Summary of Contents for D30D00HCHF8AH6AM6BP8BX7A
Page 10: ...x D30 Line Distance Protection System GE Multilin TABLE OF CONTENTS...
Page 374: ...5 248 D30 Line Distance Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5...
Page 398: ...6 24 D30 Line Distance Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6...
Page 410: ...7 12 D30 Line Distance Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7...
Page 444: ...9 24 D30 Line Distance Protection System GE Multilin 9 5 FAULT LOCATOR 9 THEORY OF OPERATION 9...
Page 576: ...B 102 D30 Line Distance Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B...
Page 616: ...D 10 D30 Line Distance Protection System GE Multilin D 1 IEC 60870 5 104 PROTOCOL APPENDIX D D...
Page 628: ...E 12 D30 Line Distance Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E...
Page 636: ...F 8 D30 Line Distance Protection System GE Multilin F 3 WARRANTY APPENDIX F F...
Page 646: ...x D30 Line Distance Protection System GE Multilin INDEX...