B-34
D30 Line Distance Protection System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
5DA8
Ground Instantaneous Overcurrent 1 Events
0 to 1
---
1
F102
0 (Disabled)
5DA9
Reserved (8 items)
0 to 1
---
1
F001
0
5DB1
...Repeated for Ground Instantaneous Overcurrent 2
Setting Groups (Read/Write Setting)
5F70
Setting Group for Modbus Comms (0 means group 1)
0 to 5
---
1
F001
0
5F71
Setting Groups Block
0 to 4294967295
---
1
F300
0
5F73
FlexLogic Operands to Activate Groups 2 through 6 (5
items)
0 to 4294967295
---
1
F300
0
5F7D
Setting Group Function
0 to 1
---
1
F102
0 (Disabled)
5F7E
Setting Group Events
0 to 1
---
1
F102
0 (Disabled)
Setting Groups (Read Only)
5F7F
Current Setting Group
0 to 5
---
1
F001
0
Setting Group Names (Read/Write Setting)
5F8C
Setting Group 1 Name
---
---
---
F203
(none)
5F94
Setting Group 2 Name
---
---
---
F203
(none)
5F9C
Setting Group 3 Name
---
---
---
F203
(none)
5FA4
Setting Group 4 Name
---
---
---
F203
(none)
5FAC
Setting Group 5 Name
---
---
---
F203
(none)
5FB4
Setting Group 6 Name
---
---
---
F203
(none)
Autoreclose (Read/Write Setting) (1 module)
6200
Autoreclose 1 Function
0 to 1
---
1
F102
0 (Disabled)
6201
Autoreclose 1 Initiate
0 to 4294967295
---
1
F300
0
6203
Autoreclose 1 Block
0 to 4294967295
---
1
F300
0
6205
Autoreclose 1 Max Number of Shots
1 to 4
---
1
F001
1
6206
Autoreclose 1 Manual Close
0 to 4294967295
---
1
F300
0
6208
Autoreclose 1 Manual Reset from LO
0 to 4294967295
---
1
F300
0
620A
Autoreclose 1 Reset Lockout if Breaker Closed
0 to 1
---
1
F108
0 (Off)
620B
Autoreclose 1 Reset Lockout On Manual Close
0 to 1
---
1
F108
0 (Off)
620C
Autoreclose 1 Breaker Closed
0 to 4294967295
---
1
F300
0
620E
Autoreclose 1 Breaker Open
0 to 4294967295
---
1
F300
0
6210
Autoreclose 1 Block Time Upon Manual Close
0 to 655.35
s
0.01
F001
1000
6211
Autoreclose 1 Dead Time Shot 1
0 to 655.35
s
0.01
F001
100
6212
Autoreclose 1 Dead Time Shot 2
0 to 655.35
s
0.01
F001
200
6213
Autoreclose 1 Dead Time Shot 3
0 to 655.35
s
0.01
F001
300
6214
Autoreclose 1 Dead Time Shot 4
0 to 655.35
s
0.01
F001
400
6215
Autoreclose 1 Reset Lockout Delay
0 to 655.35
s
0.01
F001
6000
6216
Autoreclose 1 Reset Time
0 to 655.35
s
0.01
F001
6000
6217
Autoreclose 1 Incomplete Sequence Time
0 to 655.35
s
0.01
F001
500
6218
Autoreclose 1 Events
0 to 1
---
1
F102
0 (Disabled)
6219
Autoreclose 1 Reduce Max 1
0 to 4294967295
---
1
F300
0
621B
Autoreclose 1 Reduce Max 2
0 to 4294967295
---
1
F300
0
621D
Autoreclose 1 Reduce Max 3
0 to 4294967295
---
1
F300
0
621F
Autoreclose 1 Add Delay 1
0 to 4294967295
---
1
F300
0
6221
Autoreclose 1 Delay 1
0 to 655.35
s
0.01
F001
0
6222
Autoreclose 1 Add Delay 2
0 to 4294967295
---
1
F300
0
6224
Autoreclose 1 Delay 2
0 to 655.35
s
0.01
F001
0
6225
Reserved (4 items)
0 to 0.001
---
0.001
F001
0
Negative Sequence Time Overcurrent (Read/Write Grouped Setting) (2 modules)
6300
Negative Sequence Time Overcurrent 1 Function
0 to 1
---
1
F102
0 (Disabled)
6301
Negative Sequence Time Overcurrent 1 Signal Source
0 to 5
---
1
F167
0 (SRC 1)
6302
Negative Sequence Time Overcurrent 1 Pickup
0 to 30
pu
0.001
F001
1000
6303
Negative Sequence Time Overcurrent 1 Curve
0 to 16
---
1
F103
0 (IEEE Mod Inv)
6304
Negative Sequence Time Overcurrent 1 Multiplier
0 to 600
---
0.01
F001
100
6305
Negative Sequence Time Overcurrent 1 Reset
0 to 1
---
1
F104
0 (Instantaneous)
Table B–10: MODBUS MEMORY MAP (Sheet 26 of 58)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for D30D00HCHF8AH6AM6BP8BX7A
Page 10: ...x D30 Line Distance Protection System GE Multilin TABLE OF CONTENTS...
Page 374: ...5 248 D30 Line Distance Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5...
Page 398: ...6 24 D30 Line Distance Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6...
Page 410: ...7 12 D30 Line Distance Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7...
Page 444: ...9 24 D30 Line Distance Protection System GE Multilin 9 5 FAULT LOCATOR 9 THEORY OF OPERATION 9...
Page 576: ...B 102 D30 Line Distance Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B...
Page 616: ...D 10 D30 Line Distance Protection System GE Multilin D 1 IEC 60870 5 104 PROTOCOL APPENDIX D D...
Page 628: ...E 12 D30 Line Distance Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E...
Page 636: ...F 8 D30 Line Distance Protection System GE Multilin F 3 WARRANTY APPENDIX F F...
Page 646: ...x D30 Line Distance Protection System GE Multilin INDEX...