September 2004
2-14
Programming Site Data
Set Transducer Signal
Settings - SIGNL (cont.)
Table 2-3: Transducer Signal Settings
Transducer
Signal
Parameters
Range
Default
Value
Miscellaneous Information
Signal Low
Limit
-20 to 100
40
The
E1:LOW SIGNAL
error message appears when the
signal strength falls below the programmed
SIGNAL
LOW LIMIT
value. See Chapter 5,
Error Codes
, for a
discussion of error codes.
Correlation
Peak Limit
0 to 500
100
The
E4: SIGNAL QUALITY
error message appears when
the signal quality falls below the programmed
COR.
PEAK LIMIT
value. See Chapter 5,
Error Codes
, for a
discussion of error codes.
Soundspeed
± Limit
1 to 50%
20%
The
E2:SOUNDSPEED
error message appears when the
calculated fluid sound speed differs from the fluid
sound speed entered in the Channelx-System menu by
more than the programmed
SOUNDSPEED ± LIMIT
value. See Chapter 5,
Error Codes
, for a discussion of
error codes.
Velocity Low
Limit
–328 to 328
ft/sec
(–100 to
100 m/sec)
–40.0 ft/sec
(–12 m/sec)
The
E3: VELOCITY RANGE
error messages appears
when the calculated fluid velocity is less than the
programmed
VELOCITY LOW LIMIT
value. See
Chapter 5,
Error Codes
, for a discussion of error codes.
Velocity High
Limit
–328 to 328
ft/sec
(–100 to
100 m/sec)
40.0 ft/sec
(12 m/sec)
The
E3: VELOCITY RANGE
error messages appears
when the calculated fluid velocity exceeds the
programmed
VELOCITY HIGH LIMIT
value. See
Chapter 5,
Error Codes
, for a discussion of error codes.
Acceleration
Limit
0 to 100
ft/sec
2
(0 to 30
m/sec
2
)
15.0 ft/sec
2
(4.6 m/sec
2
)
The
E6: CYCLE SKIP
error message appears when the
calculated fluid velocity changes by more than the
programmed
ACCLERATION LIMIT
value from one
reading to the next. See Chapter 5,
Error Codes
, for a
discussion of error codes.
Amplitude
Discriminator
Low
0 to 100
14
The amplitude measures the transducer signal received
by the Model AT868. The
E5: AMPLITUDE
error
message appears when the amplitude discriminator
falls below the programmed
AMP. DISCRIM. LOW
value.
See Chapter 5,
Error Codes
, for a discussion of error
codes.
Amplitude
Discriminator
High
0 to 100
34
The amplitude discriminator measures the transducer
signal received by the Model AT868. The
E5: AMPLITUDE
error message appears when the
amplitude discriminator exceeds the programmed
AMP.
DISCRIM. LOW
value. See Chapter 5,
Error Codes
, for a
discussion of error codes.
Summary of Contents for AquaTrans AT868
Page 8: ...Chapter 1 ...
Page 24: ...Chapter 2 ...
Page 60: ...Chapter 3 ...
Page 66: ...Chapter 4 ...
Page 72: ...Chapter 5 ...
Page 77: ...Chapter 6 ...
Page 88: ...Chapter 7 ...
Page 98: ...Chapter 8 ...
Page 106: ...Appendix A ...
Page 112: ...Appendix B ...
Page 113: ...CE Mark Compliance Introduction B 1 EMC Compliance B 1 LVD Compliance B 2 ...
Page 116: ...Appendix C ...
Page 117: ...Data Records Site Data C 1 ...
Page 122: ...Appendix D ...
Page 123: ...Measuring P and L Dimensions Measuring P and L D 1 ...
Page 126: ...Appendix E ...
Page 127: ...Service Record Introduction E 1 Data Entry E 1 Diagnostic Parameters E 3 ...
Page 131: ...Appendix F ...