Installation
1-7
September 2004
Wiring Std 0/4-20 mA
Analog Outputs
The Model AT868 flow transmitter has one isolated 0/4-20 mA
analog output per channel (designated as Output A and C). These
outputs can be configured independently. Typically, Output A is used
for Channel 1 and Output C is used for Channel 2; however, analog
outputs can be configured to measure either channel.
Connections to this output may be made with standard twisted-pair
wiring, but the current loop impedance for these circuits must not
exceed 600 ohms.
To wire the analog outputs, complete the following steps:
1.
Follow the instructions on page 1-4 to prepare the unit before you
connect power.
2.
Refer to Figure 1-4 on page 1-14 for the locations of the
appropriate terminal blocks and wire the analog outputs as shown.
Secure the cable clamp.
Note:
Analog outputs 1 and 2 in the wiring diagram correspond to
analog outputs A and C in the AT868 software.
!ATTENTION EUROPEAN CUSTOMERS!
To meet CE Mark requirements, all cables must be installed
as described in Appendix B,
CE Mark Compliance
.
3.
Do one of the following:
•
Proceed to the next section to continue wiring the Model AT868
flow transmitter.
•
Reinstall the plastic shroud, replace the front cover on the
enclosure and tighten the screws.
Note:
Prior to use, the analog output must be set up and calibrated.
See Chapter 4,
Calibration
, for detailed instructions.
Summary of Contents for AquaTrans AT868
Page 8: ...Chapter 1 ...
Page 24: ...Chapter 2 ...
Page 60: ...Chapter 3 ...
Page 66: ...Chapter 4 ...
Page 72: ...Chapter 5 ...
Page 77: ...Chapter 6 ...
Page 88: ...Chapter 7 ...
Page 98: ...Chapter 8 ...
Page 106: ...Appendix A ...
Page 112: ...Appendix B ...
Page 113: ...CE Mark Compliance Introduction B 1 EMC Compliance B 1 LVD Compliance B 2 ...
Page 116: ...Appendix C ...
Page 117: ...Data Records Site Data C 1 ...
Page 122: ...Appendix D ...
Page 123: ...Measuring P and L Dimensions Measuring P and L D 1 ...
Page 126: ...Appendix E ...
Page 127: ...Service Record Introduction E 1 Data Entry E 1 Diagnostic Parameters E 3 ...
Page 131: ...Appendix F ...