Protection and Features:
•
Electronic thermal motor protection against overload.
•
Temperature monitoring of the heatsink ensures that the frequency converter trips if the temperature reaches a predefined level. An overload temper-
ature cannot be reset until the temperature of the heatsink is below the values stated in the tables on the following pages (Guideline - these temperatures
may vary for different power sizes, Unit Sizes, enclosure ratings etc.).
•
The frequency converter is protected against short-circuits on motor terminals U, V, W.
•
If a mains phase is missing, the frequency converter trips or issues a warning (depending on the load).
•
Monitoring of the intermediate circuit voltage ensures that the frequency converter trips if the intermediate circuit voltage is too low or too high.
•
The frequency converter constantly checks for critical levels of internal temperature, load current, high voltage on the intermediate circuit and low motor
speeds. As a response to a critical level, the frequency converter can adjust the switching frequency and/ or change the switching pattern in order to
ensure the performance of the drive.
Digital inputs:
Programmable digital inputs
4 (6)
1)
Terminal number
18, 19, 27
1)
, 29
1)
, 32, 33,
Logic
PNP or NPN
Voltage level
0 - 24 V DC
Voltage level, logic'0' PNP
< 5 V DC
Voltage level, logic'1' PNP
> 10 V DC
Voltage level, logic '0' NPN
2)
> 19 V DC
Voltage level, logic '1' NPN
2)
< 14 V DC
Maximum voltage on input
28 V DC
Pulse frequency range
0 - 110 kHz
(Duty cycle) Min. pulse width
4.5 ms
Input resistance, R
i
approx. 4 k
Ω
Safe stop Terminal 37
2)
(Terminal 37 is fixed PNP logic):
Voltage level
0 - 24 V DC
Voltage level, logic'0' PNP
< 4 V DC
Voltage level, logic'1' PNP
>20 V DC
Nominal input current at 24 V
50 mA rms
Nominal input current at 20 V
60 mA rms
Input capacitance
400 nF
All digital inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
1) Terminals 27 and 29 can also be programmed as output.
2) Terminal 37 is only available in AF-650 GP. It can only be used as safe stop input. Terminal 37 is suitable for category 3 installations according to EN 954-1 (safe
stop according to category 0 EN 60204-1) as required by the EU Machinery Directive 98/37/EC. Terminal 37 and the Safe Stop function are designed in conformance
with EN 60204-1, EN 50178, EN 61800-2, EN 61800-3, and EN 954-1. For correct and safe use of the Safe Stop function follow the related information and instructions
in the AF-650 GP Design Guide.
AF-650 GP Design Guide
72
4
Summary of Contents for AF-650 GP Series
Page 5: ...AF 650 GP Design Guide 4 1...
Page 53: ...AF 650 GP Design Guide 52 4...
Page 97: ...Please note airflow directions 6 1 5 Mechanical Dimensions AF 650 GP Design Guide 96 6...
Page 98: ...Please note airflow directions AF 650 GP Design Guide 97 6...
Page 99: ...Please note airflow directions AF 650 GP Design Guide 98 6...
Page 100: ...Please note airflow directions AF 650 GP Design Guide 99 6...
Page 173: ...Max cable length 150 m AF 650 GP Design Guide 172 9...
Page 179: ...AF 650 GP Design Guide 178 9...