8.1.11 LC Application Example
One sequence 1:
Start – accel – run at reference speed 2 sec – decel and hold shaft until stop.
Set the accel/decel times in par. F-07
Accel Time 1
and par. F-08
Decel Time 1
to the wanted times
tramp
=
tacc
×
nnorm
(
par
.
P
−
06)
ref
RPM
Set Preset reference 0 to first preset speed (par. C-05
Multi-step Frequency 1 - 8
[0]) in percentage of Max reference speed (par. F-53
Maximum Reference
). Ex.:
60%
Set preset reference 1 to second preset speed (par. C-05
Multi-step Frequency 1 - 8
[1] Ex.: 0 % (zero).
Set the timer 0 for constant running speed in par. LC-20
Logic Controller Timer
[0]. Ex.: 2 sec.
Set Event 1 in par. LC-51
Logic Controller Event
[1] to
True
[1]
Set Event 2 in par. LC-51
Logic Controller Event
[2] to
On Reference
[4]
Set Event 3 in par. LC-51
Logic Controller Event
[3] to
Time Out 0
[30]
Set Event 4 in par. LC-51
Logic Controller Event
[1] to
False
[0]
Set Action 1 in par. LC-52
Logic Controller Action
[1] to
Select preset 0
[10]
Set Action 2 in par. LC-52
Logic Controller Action
[2] to
Start Timer 0
[29]
Set Action 3 in par. LC-52
Logic Controller Action
[3] to
Select preset 1
[11]
Set Action 4 in par. LC-52
Logic Controller Action
[4] to
No Action
[1]
AF-650 GP Design Guide
164
8
Summary of Contents for AF-650 GP Series
Page 5: ...AF 650 GP Design Guide 4 1...
Page 53: ...AF 650 GP Design Guide 52 4...
Page 97: ...Please note airflow directions 6 1 5 Mechanical Dimensions AF 650 GP Design Guide 96 6...
Page 98: ...Please note airflow directions AF 650 GP Design Guide 97 6...
Page 99: ...Please note airflow directions AF 650 GP Design Guide 98 6...
Page 100: ...Please note airflow directions AF 650 GP Design Guide 99 6...
Page 173: ...Max cable length 150 m AF 650 GP Design Guide 172 9...
Page 179: ...AF 650 GP Design Guide 178 9...