4.4 Electrical Data - 525-600 V
Mains Supply 3 x 525 - 600 VAC
AF-650 GP
Typical Shaft Output [kW]
0.75
1.5
2.2
3
4
5.5
7.5
Typical Shaft Output [HP] at 575V
1.0
2.0
3.0
4.0
5.0
7.5
10
Unit Size IP20
13
13
13
13
13
13
13
Unit Size IP55
15
15
15
15
15
15
15
Output current
Continuous
(3 x 525-550 V ) [A]
1.8
2.9
4.1
5.2
6.4
9.5
11.5
Intermittent
(3 x 525-550 V ) [A]
2.9
4.6
6.6
8.3
10.2
15.2
18.4
Continuous
(3 x 551-600 V ) [A]
1.7
2.7
3.9
4.9
6.1
9.0
11.0
Intermittent
(3 x 551-600 V ) [A]
2.7
4.3
6.2
7.8
9.8
14.4
17.6
Continuous kVA (525 V AC) [kVA]
1.7
2.8
3.9
5.0
6.1
9.0
11.0
Continuous kVA (575 V AC) [kVA]
1.7
2.7
3.9
4.9
6.1
9.0
11.0
Max. cable size
(mains, motor, brake)
[AWG]
2)
[mm
2
]
24 - 10 AWG
0.2 - 4 mm
2
24 - 10 AWG
0.2 - 4 mm
2
Max. input current
Continuous
(3 x 525-600 V ) [A]
1.7
2.7
4.1
5.2
5.8
8.6
10.4
Intermittent
(3 x 525-600 V ) [A]
2.7
4.3
6.6
8.3
9.3
13.8
16.6
Max. mains fuses
1)
[A]
10
10
20
20
20
32
32
Environment
Estimated power loss
at rated max. load [W]
4)
35
65
92
122
145
195
261
Weight,
Unit Size IP20 [kg]
6.5
6.5
6.5
6.5
6.5
6.6
6.6
Weight,
Unit Size IP55, 66 [kg]
13.5
13.5
13.5
13.5
13.5
14.2
14.2
Efficiency
4)
0.97
0.97
0.97
0.97
0.97
0.97
0.97
AF-650 GP Design Guide
61
4
Summary of Contents for AF-650 GP Series
Page 5: ...AF 650 GP Design Guide 4 1...
Page 53: ...AF 650 GP Design Guide 52 4...
Page 97: ...Please note airflow directions 6 1 5 Mechanical Dimensions AF 650 GP Design Guide 96 6...
Page 98: ...Please note airflow directions AF 650 GP Design Guide 97 6...
Page 99: ...Please note airflow directions AF 650 GP Design Guide 98 6...
Page 100: ...Please note airflow directions AF 650 GP Design Guide 99 6...
Page 173: ...Max cable length 150 m AF 650 GP Design Guide 172 9...
Page 179: ...AF 650 GP Design Guide 178 9...