Mains Supply 3 x 380 - 480 VAC
AF-650 GP
350 HP
450 HP
500 HP
550 HP
Heavy Duty/Light Duty*
HD
LD
HD
LD
HD
LD
HD
LD
Typical Shaft output at 400 V
[kW]
250
315
315
355
355
400
400
450
Typical Shaft output at 460 V
[HP]
350
450
450
500
500
600
550
600
Typical Shaft output at 480 V
[kW]
315
355
355
400
400
500
500
530
IP21/Nema 1 Drive Type
51
51
51
51
IP54/Nema 12 Drive Type
51
51
51
51
IP00 Open Chassis Drive
Type
52
52
52
52
Output current
Continuous
(at 400 V) [A]
480
600
600
658
658
745
695
800
Intermittent (60 sec over-
load)
(at 400 V) [A]
720
660
900
724
987
820
1043
880
Continuous
(at 460/ 480 V) [A]
443
540
540
590
590
678
678
730
Intermittent (60 sec over-
load)
(at 460/ 480 V) [A]
665
594
810
649
885
746
1017
803
Continuous KVA
(at 400 V) [KVA]
333
416
416
456
456
516
482
554
Continuous KVA
(at 460 V) [KVA]
353
430
430
470
470
540
540
582
Continuous KVA
(at 480 V) [KVA]
384
468
468
511
511
587
587
632
Max. input current
Continuous
(at 400 V ) [A]
472
590
590
647
647
733
684
787
Continuous
(at 460/ 480 V) [A]
436
531
531
580
580
667
667
718
Max. cable size, mains, mo-
tor and load share [mm
2
(AWG
2)
)]
4x240
(4x500 mcm)
4x240
(4x500 mcm)
4x240
(4x500 mcm)
4x240
(4x500 mcm)
Max. cable size, brake [mm
2
(AWG
2)
)
2 x 185
(2 x 350 mcm)
2 x 185
(2 x 350 mcm)
2 x 185
(2 x 350 mcm)
2 x 185
(2 x 350 mcm)
Max. external mains fuses
[A]
1
700
900
900
900
Estimated power loss
at 400 V [W]
4)
5164
6790
6960
7701
7691
8879
8178
9670
Estimated power loss
at 460 V [W]
4822
6082
6345
6953
6944
8089
8085
8803
Weight,
Unit Size IP21, IP 54 [kg]
263
270
272
313
Weight,
Unit Size IP00 [kg]
221
234
236
277
Efficiency
4)
0.98
Output
frequency
0 - 600 Hz
Heatsink overtemp. trip
95 °C
Power card ambient trip
68 °C
* Heavy Duty = 160% torque during 60 s, Light Duty = 110% torque during 60 s
AF-650 GP Design Guide
59
4
Summary of Contents for AF-650 GP Series
Page 5: ...AF 650 GP Design Guide 4 1...
Page 53: ...AF 650 GP Design Guide 52 4...
Page 97: ...Please note airflow directions 6 1 5 Mechanical Dimensions AF 650 GP Design Guide 96 6...
Page 98: ...Please note airflow directions AF 650 GP Design Guide 97 6...
Page 99: ...Please note airflow directions AF 650 GP Design Guide 98 6...
Page 100: ...Please note airflow directions AF 650 GP Design Guide 99 6...
Page 173: ...Max cable length 150 m AF 650 GP Design Guide 172 9...
Page 179: ...AF 650 GP Design Guide 178 9...