7.12 Final Setup and Test
To test the set-up and ensure that the frequency converter is running, follow these steps.
Step 1. Locate the motor name plate
NB!
The motor is either star- (Y) or delta- connected (
∆
). This information is located on the motor name plate data.
Step 2. Enter the motor name plate data in this parameter list.
To access this list first press the [QUICK MENU] key then select “Quick Setup”.
Use the up and down arrow keys to navigate to the parameters associated
with the motor nameplate values.
1.
Par. P-07
Motor Power [kW]
Par. P-02
Motor Power [HP]
2.
Par. F-05
Motor Rated Voltage
3.
Par. F-04
Base Frequency
4.
Par. P-03
Motor Current
5.
Par. P-06
Base Speed
Step 3. Activate the Auto Tune
Performing an Auto Tune will ensure optimum performance. The Auto Tune measures the values from the motor model equivalent diagram.
1.
Connect terminal 37 to terminal 12.
2.
Activate the Auto Tune par. P-04
Auto Tune
.
3.
Choose between complete or reduced Auto Tune. If a Sine-wave filter is connected, run only the reduced Auto Tune, or remove the Sine-wave filter and
run complete Auto Tune..
4.
Press the [OK] key. The display shows “Press [Hand] to start”.
5.
Press the [Hand] key. A progress bar indicates if the Auto Tune is in progress.
Stop the Auto Tune during operation
1.
Press the [OFF] key - the frequency converter enters into alarm mode and the display shows that the Auto Tune was terminated by the user.
Successful Auto Tune
1.
The display shows “Press [OK] to finish Auto Tune”.
2.
Press the [OK] key to exit the Auto Tune state.
AF-650 GP Design Guide
157
7
Summary of Contents for AF-650 GP Series
Page 5: ...AF 650 GP Design Guide 4 1...
Page 53: ...AF 650 GP Design Guide 52 4...
Page 97: ...Please note airflow directions 6 1 5 Mechanical Dimensions AF 650 GP Design Guide 96 6...
Page 98: ...Please note airflow directions AF 650 GP Design Guide 97 6...
Page 99: ...Please note airflow directions AF 650 GP Design Guide 98 6...
Page 100: ...Please note airflow directions AF 650 GP Design Guide 99 6...
Page 173: ...Max cable length 150 m AF 650 GP Design Guide 172 9...
Page 179: ...AF 650 GP Design Guide 178 9...