7.6.5 Electrical Installation, Control Terminals
To mount the cable to the terminal:
1.
Strip insulation of 9-10 mm
2.
Insert a screwdriver
1)
in the square hole.
3.
Insert the cable in the adjacent circular hole.
4.
Remove the screw driver. The cable is now mounted to the terminal.
To remove the cable from the terminal:
1.
Insert a screwdriver
1)
in the square hole.
2.
Pull out the cable.
1)
Max. 0.4 x 2.5 mm
1.
2.
3.
AF-650 GP Design Guide
145
7