AF-650 GP 460V 60 HP
Cable
length [m]
Mains
voltage [V]
Rise time
[
μ
sec]
Upeak
[kV]
du/dt
[kV/
μ
sec]
15
480
0.256
1.230
3.847
50
480
0.328
1.200
2.957
100
480
0.456
1.200
2.127
150
480
0.960
1.150
1.052
AF-650 GP 460V 75 HP
Cable
length [m]
Mains
voltage [V]
Rise time
[
μ
sec]
Upeak
[kV]
du/dt
[kV/
μ
sec]
5
480
0.371
1.170
2.523
AF-650 GP 460V 100 HP
Cable
length [m]
Mains
voltage [V]
Rise time
[
μ
sec]
Upeak
[kV]
du/dt
[kV/
μ
sec]
5
480
0.371
1.170
2.523
High Power range:
The power sizes below at the appropriate mains voltages comply with the requirements of IEC 60034-17 regarding normal motors controlled by frequency
converters, IEC 60034-25 regarding motors designed to be controlled by frequency converters, and NEMA MG 1-1998 Part 31.4.4.2 for inverter fed motors. The
power sizes below do not comply with NEMA MG 1-1998 Part 30.2.2.8 for general purpose motors.
90 - 200 kW / 380-480 V
Cable
length
Mains
voltage
Rise time
Peak
voltage
du/dt
30 metres
400 V
0.34
µ
sec.
1040 V
2447 V/
µ
sec.
250 - 800 kW / 380-480 V
Cable
length
Mains
voltage
Rise time
Peak
voltage
du/dt
30 metres
480 V
0.71
µ
sec.
1165 V
1389 V/
µ
sec.
30 metres
480 V
1)
0.80
µ
sec.
906 V
904 V/
µ
sec.
30 metres
400 V
0.61
µ
sec.
942 V
1233 V/
µ
sec.
30 metres
400 V
1)
0.82
µ
sec.
760 V
743 V/
µ
sec.
1) With GE du/dt filter
90 - 315 kW/ 525-690 V
Cable
length
Mains
voltage
Rise time
Peak
voltage
du/dt
30 metres
690 V
0.38
µ
sec.
1573
3309 V/
µ
sec.
30 metres
690 V
1)
1.72
µ
sec.
1329
640 V/
µ
sec.
30 metres
575 V
0.23
µ
sec.
1314
2750 V/
µ
sec.
30 metres
575 V
2)
0.72
µ
sec.
1061
857 V/
µ
sec.
1) With GE du/dt filter
2) With du/dt filter
355 - 1000 kW / 525-690 V
Cable
length
Mains
voltage
Rise time
Peak
voltage
du/dt
30 metres
690 V
0.57
µ
sec.
1611
2261 V/
µ
sec.
30 metres
575 V
0.25
µ
sec.
2510 V/
µ
sec.
30 metres
690 V
1)
1.13
µ
sec.
1629
1150 V/
µ
sec.
1) With GE du/dt filter.
AF-650 GP Design Guide
80
4
Summary of Contents for AF-650 GP Series
Page 5: ...AF 650 GP Design Guide 4 1...
Page 53: ...AF 650 GP Design Guide 52 4...
Page 97: ...Please note airflow directions 6 1 5 Mechanical Dimensions AF 650 GP Design Guide 96 6...
Page 98: ...Please note airflow directions AF 650 GP Design Guide 97 6...
Page 99: ...Please note airflow directions AF 650 GP Design Guide 98 6...
Page 100: ...Please note airflow directions AF 650 GP Design Guide 99 6...
Page 173: ...Max cable length 150 m AF 650 GP Design Guide 172 9...
Page 179: ...AF 650 GP Design Guide 178 9...