[18]
Reversing
See par. 5-4* [25] for description.
[19]
Warning
A warning is active.
[20]
Alarm_Trip
A trip alarm is active.
[21]
Alarm_TripLock
A trip lock alarm is active.
[22]
Comparator 0
Use result of comparator 0 in logic rule.
[23]
Comparator 1
Use result of comparator 1 in logic rule.
[24]
Comparator 2
Use result of comparator 2 in logic rule.
[25]
Comparator 3
Use result of comparator 3 in logic rule.
[26]
LogicRule 0
Use result of logic rule 0 in logic rule.
[27]
LogicRule 1
Use result of logic rule 1 in logic rule.
[28]
LogicRule 2
Use result of logic rule 2 in logic rule.
[29]
LogicRule 3
Use result of logic rule 3 in logic rule.
[30]
LC Timeout0
Use result of timer 0 in logic rule.
[31]
LC Timeout1
Use result of timer 1 in logic rule.
[32]
LC Timeout2
Use result of timer 2 in logic rule.
[33]
DigitalInput_18
Use value of DI 18 in logic rule.
[34]
DigitalInput_19
Use value of DI 19 in logic rule.
[35]
DigitalInput_27
Use value of DI 27 in logic rule.
[36]
DigitalInput_29
Use value of DI 29 in logic rule.
[38]
DigitalInput_33
[39]
StartCommand
This event is
True
, if frequency converter is started by any means (digital input or other).
[40]
*
DriveStopped
This event is
True
, if frequency converter is stopped or coasted by any means (digital input or other).
13-03 Reset Logic Controller
Option:
Function:
[0]
*
Do Not Reset
Retains all settings programmed in parameter group 13.
[1]
Reset Logic Controller
Reset all group 13 parameters to default settings.
4.10.3. 13-1* Comparators
Comparators are used for comparing continuous variables (i.e. output frequency, output current, analog input etc.) to fixed preset values. In addition, there are
digital values that will be compared to fixed time values. See explanation in par. 13-10. Comparators are evaluated once in each scan interval. Use the result
(TRUE or FALSE) directly. All parameters in this parameter group are array parameters with index 0 to 5. Select index 0 to programme Comparator 0, select index
1 to programme Comparator 1, and so on.
13-10 Comparator Operand
Array [4]
Select variable to be monitored by comparator.
[0]
*
Disabled
Comparator is disabled.
[1]
Reference
Resulting remote reference (not local) as a percentage.
[2]
Feedback
Feedback in [Hz].
[3]
MotorSpeed
Motor speed in Hz.
[4]
MotorCurrent
Motor current in [A].
[6]
MotorPower
Motor power in either [kW] or [hp].
[7]
MotorVoltage
Motor voltage in [V].
[8]
DCLinkVoltage
DC-link voltage in [V].
[12]
AnalogInput53
Expressed as a percentage.
[13]
AnalogInput60
Expressed as a percentage.
[18]
PulseInput33
Expressed as a percentage.
AF-60 LP™ Micro Drive Programming Guide
49
4