Auto:
In Auto-mode the frequency converter can be remote controlled (bus/digital).
0-40 [Hand ] Key on Keypad
Option:
Function:
[0]
Disabled
Hand key has no function.
[1 ]
*
Enabled
Hand key is functional.
0-41 [Off/Reset] Key on Keypad
Option:
Function:
[0]
Disable Off/Reset
Off/reset key has no function.
[1 ]
*
Enable Off/Reset
Stop signal and reset of any faults.
[2]
Enable Reset Only
Reset only. Stop (Off) function is disabled.
0-42 [Auto ] Key on Keypad
Option:
Function:
[0]
Disabled
Auto key has no function.
[1 ]
*
Enabled
Auto key is functional.
4.1.5. 0-5* Copy/Save
0-50 Keypad Copy
Option:
Function:
The detachable Keypad of the frequency converter can be used for storing setups, and thus for transferring data when
moving parameter settings from one frequency converter to another.
NB!
Keypad Copy
can only be activated from the Keypad and ONLY when the motor is coasted.
[1]
All to Keypad
Copy all setups from the frequency converter into the Keypad.
[2]
All from Keypad
Copy all setups from Keypad to frequency converter.
[3]
Size indep. from Keypad Copy non motor size dependent data from Keypad to frequency converter
0-51 Set-up Copy
Option:
Function:
Use this function to copy a set-up content into the
Edit Set-up
.
In order to be able to make a set-up copy ensure that
•
the motor is coasted
•
par. 0-10,
Active Set-up
, is set to either
Set-up 1
[1] or
Set-up 2
[2]
NB!
The keyboard/parameter database are blocked while Set-up Copy is running.
[0 ]
*
No Copy
Copy function is inactive
[1]
Copy from Set-up 1
Copy from
Set-up 1
to edit set-up chosen in par. 0-11,
Edit Set-up
.
[2]
Copy from Set-up 2
Copy from
Set-up 2
to edit set-up chosen in par. 0-11,
Edit Set-up
.
[9]
Copy from Factory Set-
up
Copy from Factory Settings to edit set-up chosen in par. 0-11,
Edit set-up
.
4.1.6. 0-6* Password
0-60 (Main) Menu Password
Range:
Function:
Use password for protection against unintended change of sensitive parameters, eg. motor parameters.
Password protected parameters can always be read, but cannot be edited without entering the password.
AF-60 LP™ Micro Drive Programming Guide
13
4