4.9.4. 8-30 Protocol
8-30 Protocol
Option:
Function:
Select the protocol to be used. Note that changing protocol will not be effective until after powering off the frequency
converter.
[0]
*
GE Drive Protocol
[2]
Modbus RTU
8-31 Address
Range:
Function:
Select the address for the bus.
1
*
[1 - 126]
Drive-bus range is 1-126.
Modbus range is 1-247.
8-32 Drive Port Baud Rate
Option:
Function:
Select baud rate for Drive Port.
NB!
Changing baud rate will be effective after responding to any ongoing bus-requests.
[0]
2400 Baud
[1]
4800 Baud
[2]
*
9600 Baud
[3]
19200 Baud
[4]
38400 Baud
8-33 Drive Port Parity
Option:
Function:
This parameter only affects Modbus as Drive bus always has even parity.
[0]
*
Even Parity (1 stopbit)
[1]
Odd parity
[2]
No Parity (1 stopbit)
Select this for Modbus RTU
[3]
No Parity (2 stopbit)
8-35 Minimum Response Delay
Range:
Function:
0.010 s
*
[0.001 - 0.500 s]
Specify minimum delay time between receiving a request and transmitting a response.
8-36 Max Response Delay
Range:
Function:
5.000 s
*
[0.010 - 10.00 s]
Specify maximum permissible delay time between transmitting a request and receiving a response. Exceeding this time
delay causes control word timeout.
4.9.5. 8-5* Digital/Bus
Parameters for configuring control word Digital/Bus merging.
NB!
Parameters are only active when par. 8-01,
Control SIte
, is set to
Digital and control word
[0].