[0]
*
No Operation
[80]
Logic Controller Digital
Output A
See par. 13-52
Logic Controller Action
. When Logic ControllerAction
Set dig. out. A high
[38] is executed, input goes
high. When Smart Logic Action
Set dig. out. A low
[32] is executed, input goes low.
6-93 Terminal 42 Output Min. Scale
Range:
Function:
0.00 % [0.00 - 200.0%]
Scale minimum output of selected analog signal at terminal 42 as percentage of maximum signal value. E.g. if 0 mA
(or 0 Hz) is desired at 25% of maximum output value, programme 25%. Scaling values up to 100% can never be higher
than corresponding setting in par. 6-52.
6-94 Terminal 42 Output Max. Scale
Range:
Function:
100.00%
*
[0.00 - 200.00%]
Scale maximum output of selected analog signal at terminal 42. Set value to maximum value of current signal output.
Scale output to give a current lower than 20 mA at full scale; or 20 mA at an output below 100% of maximum signal
value.
If 20 mA is the desired output current at a value between 0 - 100% of the full-scale output, programme percentage
value in the parameter, i.e. 50% = 20 mA. If a current between 4 and 20 mA is desired at maximum output (100%),
calculate percentage value as follows:
20
mA
desired maximum current
× 100 %
i.e.
10
mA
=
20
10
× 100 = 200 %
AF-60 LP™ Micro Drive Programming Guide
40
4