16-12 Motor Voltage
Range:
Function:
0.0
*
[0.0 - 999.9 V]
View motor phase voltage.
16-13 Frequency
Range:
Function:
0.0 Hz
*
[0.0 - 400.0 Hz]
View output frequency in Hz.
16-14 Motor Current
Range:
Function:
0.00 A
*
[0.00 - 655 A]
View motor phase current.
16-15 Frequency [%]
Range:
Function:
0.00
*
[-100.00 - 100.00%]
View a two-byte word reporting actual motor frequency as a percentage of par. X-XX
16-18 Motor Thermal
Range:
Function:
0%
*
[0 - 100%]
View calculated thermal motor load as percentage of estimated thermal motor load.
4.13.5. 16-3* Drive Status
Parameters for reporting the status of the frequency converter.
16-30 DC Link Voltage
Range:
Function:
0 V
*
[0 - 10000 V]
View DC-link voltage.
16-34 Heat Sink Temp.
Range:
Function:
0
*
[0 - 255
r
C]
View heat sink temperature of frequency converter.
16-35 Drive Thermal
Range:
Function:
0%
*
[0 - 100%]
View calculated thermal load on frequency converter in relation to estimated thermal load on frequency converter.
16-36 Drive Nom. Current
Range:
Function:
0.00 A
*
[0.01 - 655A]
View continuous nominal drive current.
16-37 Drive Max. Current
Range:
Function:
0.00 A
*
[0.1 - 655A]
View intermittent maximum drive current (150%).
16-38 Logic Controller State
Range:
Function:
0
*
[0 - 255]
View number of active Logic state.
4.13.6. 16-5* Ref. & Feedb.
Parameters for reporting the reference and feedback input.
AF-60 LP™ Micro Drive Programming Guide
59
4