[5]
Not and
Evaluates expression NOT [13-40/13-42] and [13-44].
[6]
Not or
Evaluates expression NOT [13-40/13-42] OR [13-44].
[7]
Not and not
Evaluates expression NOT [13-40/13-42] AND NOT [13-44].
[8]
Not or not
Evaluates expression NOT [13-40/13-42] OR NOT [13-44].
13-44 Logic Rule Boolean 3
Array [4]
Select third boolean input for selected logic rule.
See par. 13-40 for choices and descriptions.
4.10.6. 13-5* States
Parameters for programming the Logic Controller.
13-51 Logic Controller Event
Array [20]
Select boolean input to define Logic Controller Event.
See par. 13-40 for choices and descriptions.
13-52 LC Controller Action
Array [20]
Select action corresponding to LC event. Actions are executed when corresponding event (par. 13-51) is evaluated as
True
.
[0]
*
Disabled
Function is disabled.
[1]
No Action
No action is taken.
[2]
Select Set-up1
Changes active set-up to Set-up 1.
[3]
Select Set-up2
Changes active set-up to Set-up 2.
[10]
SelectPresetRef0
Selects preset reference 0
[11]
SelectPresetRef1
Selects preset reference 1
[12]
SelectPresetRef2
Selects preset reference 2
[13]
SelectPresetRef3
Selects preset reference 3
[14]
SelectPresetRef4
Selects preset reference 4
[15]
SelectPresetRef5
Selects preset reference 5
[16]
SelectPresetRef6
Selects preset reference 6
[17]
SelectPresetRef7
Selects preset reference 7
[18]
SelectRamp1
Selects ramp 1
[19]
SelectRamp2
Selects ramp 2
[22]
Run
Issues start command to frequency converter.
[23]
RunReverse
Issues start reverse command to frequency converter.
[24]
Stop
Issues stop command to frequency converter.
[25]
Qstop
Issues quick stop command to frequency converter.
[26]
DCstop
Issues DC stop command to frequency converter.
[27]
Coast
Frequency converter coasts immediately. All stop commands including coast command stop the Logic Controller.
[28]
Freeze Output
Freezes output frequency.
[29]
StartTimer0
Starts timer 0.
[30]
StartTimer1
Starts timer 1
[31]
StartTimer2
Starts timer 2
[32]
SetDO42Low
Set Digital output 42 low.
[33]
SetRelayLow
Set Relay low.
[38]
SetDO42High
Set Digital output 42 high.