B-32
F35 Multiple Feeder Protection System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
Switch (Read/Write Setting) (6 modules)
8300
Switch 1 Function
0 to 1
---
1
F102
0 (Disabled)
8301
Switch 1 Argument A Bits (8 items)
0 to 65535
---
1
F300
0
8309
Switch 1 Argument B Bits (8 items)
0 to 65535
---
1
F300
0
8311
Switch 1 Control
0 to 65535
---
1
F300
0
8312
Reserved (6 items)
0 to 65535
---
1
F001
0
8318
...Repeated for Switch 2
8330
...Repeated for Switch 3
8348
...Repeated for Switch 4
8360
...Repeated for Switch 5
8378
...Repeated for Switch 6
EGD Fast Production Status (Read Only)
83E0
EGD Fast Producer Exchange 1 Signature
0 to 65535
---
1
F001
0
83E1
EGD Fast Producer Exchange 1 Configuration Time
0 to 4294967295
---
---
F003
0
83E3
EGD Fast Producer Exchange 1 Size
0 to 65535
---
1
F001
0
EGD Slow Production Status (Read Only) (2 modules)
83F0
EGD Slow Producer Exchange 1 Signature
0 to 65535
---
1
F001
0
83F1
EGD Slow Producer Exchange 1 Configuration Time
0 to 4294967295
---
---
F003
0
83F3
EGD Slow Producer Exchange 1 Size
0 to 65535
---
1
F001
0
83F4
...Repeated for module number 2
EGD Fast Production (Read/Write Setting)
8400
EGD Fast Producer Exchange 1 Function
0 to 1
---
1
F102
0 (Disabled)
8401
EGD Fast Producer Exchange 1 Destination
0 to 4294967295
---
1
F003
0
8403
EGD Fast Producer Exchange 1 Data Rate
50 to 1000
ms
50
F001
1000
8404
EGD Fast Producer Exchange 1 Data Item 1 (20 items)
0 to 65535
---
1
F001
0
8418
Reserved (80 items)
---
---
---
F001
0
EGD Slow Production (Read/Write Setting) (2 modules)
8500
EGD Slow Producer Exchange 1 Function
0 to 1
---
1
F102
0 (Disabled)
8501
EGD Fast Producer Exchange 1 Destination
0 to 4294967295
---
1
F003
0
8503
EGD Slow Producer Exchange 1 Data Rate
500 to 1000
ms
50
F001
1000
8504
EGD Slow Producer Exchange 1 Data Item 1 (50 items)
0 to 65535
---
1
F001
0
8536
Reserved (50 items)
---
---
---
F001
0
8568
...Repeated for EGD Exchange 2
FlexState Settings (Read/Write Setting)
8800
FlexState Parameters (256 items)
---
---
---
F300
0
Digital Elements (Read/Write Setting) (48 modules)
8A00
Digital Element 1 Function
0 to 1
---
1
F102
0 (Disabled)
8A01
Digital Element 1 Name
---
---
---
F203
“Dig Element 1“
8A09
Digital Element 1 Input
0 to 65535
---
1
F300
0
8A0A
Digital Element 1 Pickup Delay
0 to 999999.999
s
0.001
F003
0
8A0C
Digital Element 1 Reset Delay
0 to 999999.999
s
0.001
F003
0
8A0E
Digital Element 1 Block
0 to 65535
---
1
F300
0
8A0F
Digital Element 1 Target
0 to 2
---
1
F109
0 (Self-reset)
8A10
Digital Element 1 Events
0 to 1
---
1
F102
0 (Disabled)
8A11
Digital Element 1 Pickup LED
0 to 1
---
1
F102
1 (Enabled)
8A12
Reserved (2 items)
---
---
---
F001
0
8A14
...Repeated for Digital Element 2
8A28
...Repeated for Digital Element 3
8A3C
...Repeated for Digital Element 4
8A50
...Repeated for Digital Element 5
8A64
...Repeated for Digital Element 6
8A78
...Repeated for Digital Element 7
8A8C
...Repeated for Digital Element 8
8AA0
...Repeated for Digital Element 9
Table B–9: MODBUS MEMORY MAP (Sheet 25 of 48)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for F35
Page 2: ......
Page 4: ......
Page 296: ...5 174 F35 Multiple Feeder Protection System GE Multilin 5 9 TESTING 5 SETTINGS 5 ...
Page 328: ...7 8 F35 Multiple Feeder Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 350: ...A 16 F35 Multiple Feeder Protection System GE Multilin A 1 PARAMETER LIST APPENDIXA A ...
Page 422: ...B 72 F35 Multiple Feeder Protection System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Page 472: ...E 12 F35 Multiple Feeder Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...