B-52
F35 Multiple Feeder Protection System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
CAD9
Direct I/O Channel 2 CRC Alarm Message Count
100 to 10000
---
1
F001
600
CADA
Direct Input/Output Channel 2 CRC Alarm Threshold
1 to 1000
---
1
F001
10
CADB
Direct Input/Output Channel 2 CRC Alarm Events
0 to 1
---
1
F102
0 (Disabled)
CADC
Reserved (4 items)
1 to 1000
---
1
F001
10
CAE0
Direct I/O Ch 1 Unreturned Messages Alarm Function
0 to 1
---
1
F102
0 (Disabled)
CAE1
Direct I/O Ch 1 Unreturned Messages Alarm Msg Count
100 to 10000
---
1
F001
600
CAE2
Direct I/O Ch 1 Unreturned Messages Alarm Threshold
1 to 1000
---
1
F001
10
CAE3
Direct I/O Ch 1 Unreturned Messages Alarm Events
0 to 1
---
1
F102
0 (Disabled)
CAE4
Reserved (4 items)
1 to 1000
---
1
F001
10
CAE8
Direct IO Ch 2 Unreturned Messages Alarm Function
0 to 1
---
1
F102
0 (Disabled)
CAE9
Direct I/O Ch 2 Unreturned Messages Alarm Msg Count
100 to 10000
---
1
F001
600
CAEA
Direct I/O Ch 2 Unreturned Messages Alarm Threshold
1 to 1000
---
1
F001
10
CAEB
Direct I/O Channel 2 Unreturned Messages Alarm Events
0 to 1
---
1
F102
0 (Disabled)
CAEC
Reserved (4 items)
---
---
1
F001
10
Remote Devices (Read/Write Setting) (16 modules)
CB00
Remote Device 1 GSSE/GOOSE Application ID
---
---
---
F209
“Remote Device 1“
CB21
Remote Device 1 GOOSE Ethernet APPID
0 to 16383
---
1
F001
0
CB22
Remote Device 1 GOOSE Dataset
0 to 8
---
1
F184
0 (Fixed)
CB23
...Repeated for Device 2
CB46
...Repeated for Device 3
CB69
...Repeated for Device 4
CB8C
...Repeated for Device 5
CBAF
...Repeated for Device 6
CBD2
...Repeated for Device 7
CBF5
...Repeated for Device 8
CC18
...Repeated for Device 9
CC3B
...Repeated for Device 10
CC5E
...Repeated for Device 11
CC81
...Repeated for Device 12
CCA4
...Repeated for Device 13
CCC7
...Repeated for Device 14
CCEA
...Repeated for Device 15
CD0D
...Repeated for Device 16
Remote Inputs (Read/Write Setting) (64 modules)
CFA0
Remote Input 1 Device
1 to 16
---
1
F001
1
CFA1
Remote Input 1 Item
0 to 64
---
1
F156
0 (None)
CFA2
Remote Input 1 Default State
0 to 3
---
1
F086
0 (Off)
CFA3
Remote Input 1 Events
0 to 1
---
1
F102
0 (Disabled)
CFA4
Remote Input 1 Name
1 to 64
---
1
F205
“Rem Ip 1”
CFAA
...Repeated for Remote Input 2
CFB4
...Repeated for Remote Input 3
CFBE
...Repeated for Remote Input 4
CFC8
...Repeated for Remote Input 5
CFD2
...Repeated for Remote Input 6
CFDC
...Repeated for Remote Input 7
CFE6
...Repeated for Remote Input 8
CFF0
...Repeated for Remote Input 9
CFFA
...Repeated for Remote Input 10
D004
...Repeated for Remote Input 11
D00E
...Repeated for Remote Input 12
D018
...Repeated for Remote Input 13
D022
...Repeated for Remote Input 14
D02C
...Repeated for Remote Input 15
D036
...Repeated for Remote Input 16
Table B–9: MODBUS MEMORY MAP (Sheet 45 of 48)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for F35
Page 2: ......
Page 4: ......
Page 296: ...5 174 F35 Multiple Feeder Protection System GE Multilin 5 9 TESTING 5 SETTINGS 5 ...
Page 328: ...7 8 F35 Multiple Feeder Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 350: ...A 16 F35 Multiple Feeder Protection System GE Multilin A 1 PARAMETER LIST APPENDIXA A ...
Page 422: ...B 72 F35 Multiple Feeder Protection System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Page 472: ...E 12 F35 Multiple Feeder Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...