1814
Source 1 Ground Current RMS
0 to 999999.999
A
0.001
F060
0
1816
Source 1 Ground Current Magnitude
0 to 999999.999
A
0.001
F060
0
1818
Source 1 Ground Current Angle
-359.9 to 0
degrees
0.1
F002
0
1819
Source 1 Zero Sequence Current Magnitude
0 to 999999.999
A
0.001
F060
0
181B
Source 1 Zero Sequence Current Angle
-359.9 to 0
degrees
0.1
F002
0
181C
Source 1 Positive Sequence Current Magnitude
0 to 999999.999
A
0.001
F060
0
181E
Source 1 Positive Sequence Current Angle
-359.9 to 0
degrees
0.1
F002
0
181F
Source 1 Negative Sequence Current Magnitude
0 to 999999.999
A
0.001
F060
0
1821
Source 1 Negative Sequence Current Angle
-359.9 to 0
degrees
0.1
F002
0
1822
Source 1 Differential Ground Current Magnitude
0 to 999999.999
A
0.001
F060
0
1824
Source 1 Differential Ground Current Angle
-359.9 to 0
degrees
0.1
F002
0
1825
Reserved (27 items)
---
---
---
F001
0
1840
...Repeated for Source 2
1880
...Repeated for Source 3
18C0
...Repeated for Source 4
1900
...Repeated for Source 5
1940
...Repeated for Source 6
Source Voltage (Read Only) (6 modules)
1A00
Source 1 Phase AG Voltage RMS
V
F060
0
1A02
Source 1 Phase BG Voltage RMS
V
F060
0
1A04
Source 1 Phase CG Voltage RMS
V
F060
0
1A06
Source 1 Phase AG Voltage Magnitude
0 to 999999.999
V
0.001
F060
0
1A08
Source 1 Phase AG Voltage Angle
-359.9 to 0
degrees
0.1
F002
0
1A09
Source 1 Phase BG Voltage Magnitude
0 to 999999.999
V
0.001
F060
0
1A0B
Source 1 Phase BG Voltage Angle
-359.9 to 0
degrees
0.1
F002
0
1A0C
Source 1 Phase CG Voltage Magnitude
0 to 999999.999
V
0.001
F060
0
1A0E
Source 1 Phase CG Voltage Angle
-359.9 to 0
degrees
0.1
F002
0
1A0F
Source 1 Phase AB or AC Voltage RMS
0 to 999999.999
V
0.001
F060
0
1A11
Source 1 Phase BC or BA Voltage RMS
0 to 999999.999
V
0.001
F060
0
1A13
Source 1 Phase CA or CB Voltage RMS
0 to 999999.999
V
0.001
F060
0
1A15
Source 1 Phase AB or AC Voltage Magnitude
0 to 999999.999
V
0.001
F060
0
1A17
Source 1 Phase AB or AC Voltage Angle
-359.9 to 0
degrees
0.1
F002
0
1A18
Source 1 Phase BC or BA Voltage Magnitude
0 to 999999.999
V
0.001
F060
0
1A1A
Source 1 Phase BC or BA Voltage Angle
-359.9 to 0
degrees
0.1
F002
0
1A1B
Source 1 Phase CA or CB Voltage Magnitude
0 to 999999.999
V
0.001
F060
0
1A1D
Source 1 Phase CA or CB Voltage Angle
-359.9 to 0
degrees
0.1
F002
0
1A1E
Source 1 Auxiliary Voltage RMS
V
F060
0
1A20
Source 1 Auxiliary Voltage Magnitude
0 to 999999.999
V
0.001
F060
0
1A22
Source 1 Auxiliary Voltage Angle
-359.9 to 0
degrees
0.1
F002
0
1A23
Source 1 Zero Sequence Voltage Magnitude
0 to 999999.999
V
0.001
F060
0
1A25
Source 1 Zero Sequence Voltage Angle
-359.9 to 0
degrees
0.1
F002
0
1A26
Source 1 Positive Sequence Voltage Magnitude
0 to 999999.999
V
0.001
F060
0
1A28
Source 1 Positive Sequence Voltage Angle
-359.9 to 0
degrees
0.1
F002
0
1A29
Source 1 Negative Sequence Voltage Magnitude
0 to 999999.999
V
0.001
F060
0
1A2B
Source 1 Negative Sequence Voltage Angle
-359.9 to 0
degrees
0.1
F002
0
1A2C
Reserved (20 items)
---
---
---
F001
0
1A40
...Repeated for Source 2
1A80
...Repeated for Source 3
1AC0
...Repeated for Source 4
1B00
...Repeated for Source 5
1B40
...Repeated for Source 6
Source Power (Read Only) (6 modules)
1C00
Source 1 Three Phase Real Power
-1000000000000 to
1000000000000
W
0.001
F060
0
Table B–9: MODBUS MEMORY MAP (Sheet 4 of 48)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for F35
Page 2: ......
Page 4: ......
Page 296: ...5 174 F35 Multiple Feeder Protection System GE Multilin 5 9 TESTING 5 SETTINGS 5 ...
Page 328: ...7 8 F35 Multiple Feeder Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 350: ...A 16 F35 Multiple Feeder Protection System GE Multilin A 1 PARAMETER LIST APPENDIXA A ...
Page 422: ...B 72 F35 Multiple Feeder Protection System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...