B-38
F35 Multiple Feeder Protection System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
Digital Counter (Read/Write Setting) (8 modules)
A800
Digital Counter 1 Function
0 to 1
---
1
F102
0 (Disabled)
A801
Digital Counter 1 Name
---
---
---
F205
“Counter 1"
A807
Digital Counter 1 Units
---
---
---
F206
(none)
A80A
Digital Counter 1 Block
0 to 65535
---
1
F300
0
A80B
Digital Counter 1 Up
0 to 65535
---
1
F300
0
A80C
Digital Counter 1 Down
0 to 65535
---
1
F300
0
A80D
Digital Counter 1 Preset
–2147483647 to
2147483647
---
1
F004
0
A80F
Digital Counter 1 Compare
–2147483647 to
2147483647
---
1
F004
0
A811
Digital Counter 1 Reset
0 to 65535
---
1
F300
0
A812
Digital Counter 1 Freeze/Reset
0 to 65535
---
1
F300
0
A813
Digital Counter 1 Freeze/Count
0 to 65535
---
1
F300
0
A814
Digital Counter 1 Set To Preset
0 to 65535
---
1
F300
0
A815
Reserved (11 items)
---
---
---
F001
0
A820
...Repeated for Digital Counter 2
A840
...Repeated for Digital Counter 3
A860
...Repeated for Digital Counter 4
A880
...Repeated for Digital Counter 5
A8A0
...Repeated for Digital Counter 6
A8C0
...Repeated for Digital Counter 7
A8E0
...Repeated for Digital Counter 8
IEC 61850 received analog settings (read/write)
AA00
IEC 61850 GOOSE analog 1 default value
–1000000 to 1000000
---
0.001
F060
1000
AA02
IEC 61850 GOOSE analog input 1 mode
0 to 1
---
1
F491
0 (Default Value)
AA03
IEC 61850 GOOSE analog input 1 units
---
---
---
F207
(none)
AA05
IEC 61850 GOOSE analog input 1 per-unit base
0 to 999999999.999
---
0.001
F060
1
AA07
...Repeated for IEC 61850 GOOSE analog input 2
AA0E
...Repeated for IEC 61850 GOOSE analog input 3
AA15
...Repeated for IEC 61850 GOOSE analog input 4
AA1C
...Repeated for IEC 61850 GOOSE analog input 5
AA23
...Repeated for IEC 61850 GOOSE analog input 6
AA2A
...Repeated for IEC 61850 GOOSE analog input 7
AA31
...Repeated for IEC 61850 GOOSE analog input 8
AA38
...Repeated for IEC 61850 GOOSE analog input 9
AA3F
...Repeated for IEC 61850 GOOSE analog input 10
AA46
...Repeated for IEC 61850 GOOSE analog input 11
AA4D
...Repeated for IEC 61850 GOOSE analog input 12
AA54
...Repeated for IEC 61850 GOOSE analog input 13
AA5B
...Repeated for IEC 61850 GOOSE analog input 14
AA62
...Repeated for IEC 61850 GOOSE analog input 15
AA69
...Repeated for IEC 61850 GOOSE analog input 16
IEC 61850 GOOSE/GSSE Configuration (Read/Write Setting)
AA80
Default GOOSE/GSSE Update Time
1 to 60
s
1
F001
60
AA81
IEC 61850 GSSE Function (GsEna)
0 to 1
---
1
F102
1 (Enabled)
AA82
IEC 61850 GSSE ID
---
---
---
F209
“GSSEOut”
AAA3
IEC 61850 GOOSE Function (GoEna)
0 to 1
---
1
F102
0 (Disabled)
AAA4
IEC 61850 GSSE Destination MAC Address
---
---
---
F072
0
AAA7
IEC 61850 Standard GOOSE ID
---
---
---
F209
“GOOSEOut”
AAC8
IEC 61850 Standard GOOSE Destination MAC Address
---
---
---
F072
0
AACB
IEC 61850 GOOSE VLAN Transmit Priority
0 to 7
---
1
F001
4
AACC
IEC 61850 GOOSE VLAN ID
0 to 4095
---
1
F001
0
AACD
IEC 61850 GOOSE ETYPE APPID
0 to 16383
---
1
F001
0
AACE
Reserved (2 items)
0 to 1
---
1
F001
0
Table B–9: MODBUS MEMORY MAP (Sheet 31 of 48)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for F35
Page 2: ......
Page 4: ......
Page 296: ...5 174 F35 Multiple Feeder Protection System GE Multilin 5 9 TESTING 5 SETTINGS 5 ...
Page 328: ...7 8 F35 Multiple Feeder Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 350: ...A 16 F35 Multiple Feeder Protection System GE Multilin A 1 PARAMETER LIST APPENDIXA A ...
Page 422: ...B 72 F35 Multiple Feeder Protection System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Page 472: ...E 12 F35 Multiple Feeder Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...