15 Base Load Sequencing (BLS) (Optional)
Gardner Denver
68
15.14.3 Set Up Compressor Module (STD) Address
The DIP switches are located behind a cover on the
right hand side of the module.
Fig. 66 Position of DIP switches
The following table shows the necessary and valid DIP
switch settings for communicating with the GD Pilot TS
master:
Compressor module (STD) DIP Switch Settings
Address
DIP switch
1.2.3.4.5.6.7.8.9.10
2 0.1.0.0.0.0.0.0.0.0
3 1.1.0.0.0.0.0.0.0.0
4 0.0.1.0.0.0.0.0.0.0
1 = On (up)
0 = Off (down)
15.14.4 Terminal Designations
Terminal Designations
Terminal
Function
1
2
3
Not used
4
5
6
COM
7
Digital input
“Operation”
110..230 V
UC
8
24..48 V UC
9
COM
10
Digital input
“Motor”
110..230 V UC
11
24..48 V UC
12
COM
13
Digital input
“On-Load”
110..230 V UC
14
24..48 V UC
16
Power supply
(~)(+)
17
110..230 V AC/DC ± 10
%
(~) (-)
21
Digital output
“Remote load enabled”
COM
22
NC
23
NO
26
Digital output
“Remote load”
COM
27
NC
28
NO
29
Digital output
“Remote half load”
COM
30
NC
31
NO
Address DIP switches
0
1
Address
DIP switch
1
2
3
4
5
6
7
8
9
10
11
12
1 2 3 4
n/a
n/a
GND
A
B
0
1
1
2
3
4
5
6
7
8
9
1
Address DIP switches
9
10
11
12
SM 1948