11 Setting Up Timer Control Operation
Gardner Denver
44
3) Touch
Settings > Timer Control > Timer
Pressure Band p2 > Start/Stop Schedule
to see an overview of p2 timer settings.
Fig. 36 Overview of p2 Timer Settings
Since the p2 pressure band schedule requires the
compressor to be running during the period between
16:10 and 16:50, the Start/Stop timer needs to be
adjusted. Only two Start/Stop timer schedules need to
be set up now. One will start at 07:50 and end at 24:00,
the other starting at 0:00 and ending at 01:10.
Fig. 37 Overview of Modified Timer Settings
11.6 Enabling Timer Control Operation for
p2 Pressure Band
If timer control using pressure band p2 is required, p2
timer operation must also be enabled in
Settings >
Control > p2 Timer Enabled
.
Fig. 38 Setting Channel 3
The compressor will always revert to the p1 pressure
band by default unless:
a scheduled p2 event is currently active and
the p2 timer has been enabled in the
Control
Menu.
When both of these conditions are met, the current
pressure band indicator on the
Home
page switches to
p2 and a clock symbol indicates that this has been
activated by the p2 timer (as opposed to a
programmable input).