10 Programmable Inputs and Outputs
Gardner Denver
40
10.3.5 Fault
Activated when there has been a fault as a result of
which the compressor has shut down. This
programmable output is normally closed and opens
when a fault occurs.
10.3.6 Warning
Activated when a warning is shown on the controller
display. This programmable output is normally closed
and opens when a warning occurs.
10.3.7 Service
Activated when a service is due or overdue. This is
triggered within 200 hours of the next service being
due. This programmable output is normally closed and
opens when a service is due.
10.3.8 Warning/Service
Activated when a warning occurs or a service is due
(see above for details). This programmable output is
normally closed and opens when a warning/service
event occurs.
10.3.9 Warn./Service/Fault
Activated when a warning or fault occurs or a service is
due (see above for details). This programmable output
is normally closed and opens when a
warning/service/fault event occurs.
10.3.10 Ready for Rem. Start
Indicates the compressor has been set to start from a
remote signal, as defined in
Settings > Control >
Remote Start Enabled
(provided that the discharge
temperature is not too low and there is no fault).
10.3.11 Pressure Band p2
Indicates that the Controller is currently using Pressure
Band 2 either from the p2 Timer
or from a programmable input.
10.3.12 Timer Start
Indicates that the compressor is currently started under
timer control (within the timer schedule).