19
7100 Series Installation/Operating Manual —
P/N 9000-0447:J 08/28/08
Installation
7100-Slim Cabinet Installation
2.2.3 7100-Slim, BSM Sub-Assembly Plate Installation
1.
Insert and secure the four (4) standoffs (1/2” round, #10-32 x 7/8”) in the four-hole mounting
pattern on the 7100 Series mounting plate as shown in Location 1 of Figure 2.2.4.
2.
Mount the 7100-Slim, BSM sub-assembly plate over the standoffs on the 7100 Series
mounting plate and secure with four (4), nuts (#10-32 KEPS) as shown in Location 2 of
Figure 2.2.4.
3.
Install the Transformer on the 7100 Series mounting plate and secure with two (2), nuts (#10-
32 KEPS) as shown in Location 3 of Figure 2.2.4.
4.
Mount the 7100-Slim, BSM sub-assembly plate to the studs in the backbox and secure with
four (4), screws (#8) as shown in Locations 1 thru 4 of Figure 2.2.4.
5.
After the BSM is mounted in the backbox, install the door.
6.
When the BSM is replaced, the system must be re-programmed.
For additional information, refer to the
BSM Installation Instructions P/N 9000-0453
.
Figure 2.2.4 7100-Slim, BSM Sub-Assembly Plate Installation
NOTE:
To install the door, the door must be opened at least 90° from the backbox.
7100 S
ERIE
S, BS
M
SUB
-ASS
EMB
LY P
LATE
TRAN
SFO
RME
R
710
0 S
ER
IES
MO
UN
TIN
G P
LA
TE
STANDOFF,
1/2" ROUND
#10-32 X 7/8"
4 PLACES
NUT,
#10-32 KEPS
4 PLACES
1
1
1
2
2
2
3
3
NOTE:
7100 BSM SERIES OPTIONS:
7100-1 (1 LOOP)
7100-2 (2 LOOP)
7100-1D (1 LOOP W/DIALER)
7100-2D (2 LOOP W/DIALER)
NUTS,
#10-32 KEPS
2 PLACES