54
7100 Series Installation/Operating Manual —
P/N 9000-0447:J 08/28/08
System Programming
CONFIG. Menu Selections
Menu Tree
Display and Selections
Main
Config
Outputs
Select
[CONFIG] 1: Type 2: General Resp 3: Groups
[L,AAA ] 5: Location 6: View 7: Copy L,AAA
1: Opens Set Output Type Menu.
2: Opens Assign Output To Group(s) Menu.
3,4: Unused.
5: Opens Set SLC Device Location Menu.
6: Displays all settings for this device.
7: Copies settings of the specified device (last output
modified).
Main
Config
Outputs
Select
Type
[L,AAA] 34 Silenceable Signal AOM
Key in Output Type# or use <,>
<>: scroll through types which match this physical device #
keys: Enter type number (no restrictions: see Type Table)
Output device types cannot be edited. If the new type is an
input device, “OK” key returns to the System Config Menu,
otherwise to Output Config.
Select
General Response
[L,AAA] Activates for Day Alarm (YES)
[GNL RSP] select condition 1: YES/NO
1: Toggles specified general group membership YES/NO.
Select
I/O Group
[L,AAA] Group 1: 36 (00 = none)
[GROUPS] Key in group # <,> change
<>: scrolls through list of general groups.
Number keys: set group number.
Select
View
[L, 1AA] Slncbl NAC Main Lobby
ALd ALn ACT SPV TOR WKT TBL 02 00 00
<>: select which of the three possible groups to set.
Shows: SLC and Address, Type, Location, General responses,
Group membership. General responses show above
abbreviations.
Main
Config
Groups
[SELECT] Group number: 03
[GROUP ] Key in group# or use <,>
If the output is activated in that condition, or – if not. # keys:
enters group number.
<>: Scrolls up or down to next group.
Main
Config
Groups
Select
General
Response
[GROUP] Activates General Alarm (NO)
[ 03 ] Activates Genrl Supervisory (YES)
OK: Accepts group number, opens Configure Group Menu.
1: Toggles General Alarm response on/off (applies to alarms
initiated by Alarm, Manual, Waterflow, and Aux devices, for
both Day and Night general alarm).
2: Toggles General Supervisory response on/off (applies to off-
normals initiated by Supervisory and Tamper devices).
If a group contains inputs of several types (an unusual case),
the appropriate general flag is applied for each new alarm/off-
normal.
Table 5.2.7 Config Menu Tree Display and Selections