52
7100 Series Installation/Operating Manual —
P/N 9000-0447:J 08/28/08
System Programming
CONFIG. Menu Selections
Table 5.2.4 lists the Sensor Sensitivity Settings.
Photo Ion
Low 2.0
1.3
L/M 1.75
1.2
Med. 1.5
1.0
M/H 1.25
0.88
High 1.0
0.77
Table 5.2.4 Sensor Sensitivity Settings
Menu Tree
Display and Selections
Main
Config
Global
Codes
[CODED] 1: Set Day Alarm (MT60) Config
[PATTS] to select condition
<>: selects response condition from: Day Alarm, Night Alarm,
Action, Supervisory, Aux. 1: Scrolls through coded pattern
selections: MT60, MT120, Temporal, CA Code, Coded 4s.
Main
Config
Global
System ID
or
Main
Config
Inputs (or Outputs)
Select
Location
[L,AAA] FLR1 Lobby Config
[LOCTN] 7,9 chng 1st ^ chng 2nd
Enter label using keypad and shift key. Press button until
desired letter appears. Use BKSP/EDIT to capitalize.
Use arrow keys <> to shift message from left to right or vice
versa.
NOTE:
NOTE: If this menu is opened from the Global Config
Menu, System ID selection (Menu 5 option 4), SYSTM ID is
displayed; otherwise, L,AAA LOCTN as shown above.
1: Toggles Multiple Trouble Acknowledge ON/OFF
2: Toggles Alarm/Trouble Reminder ON/OFF
3: Scrolls Walk Test Timeout (30m, 60m, 90m)
4: Toggles RS232 Supervision Message ON/OFF
Main
Config
Global
Misc. [6]
[MISC] 1: MutiAck (ON) 2: Reminder (ON) Config
[OPTS] 3: WT Timeout (30m) 4: SupvMsg (ON)
Main
Config
Global
Misc. [7]
[LCD] Number of Remote Displays (1)
[Annunc]
Table 5.2.5 Config Menu Tree Display and Selections
NOTE:
Some menus may appear in different contexts, but with slightly different behavior. For
example, the “Select Device” menu is used in both the Config Inputs and Config Outputs sections
to determine which device is to be affected. The process of selection is the same, but when the
selection is complete, the result (that is, which menu opens next) differs.
!
WARNING: The Alarm Verification Feature is disabled when sensor cross-zoning is
employed.