7100 Series Installation/Operating Manual —
P/N 9000-0447:J 08/28/08
35
Analog Sensors
Basic System Module (BSM)
3.5 Analog Sensors
The 7100 Series accommodates only Gamewell-FCI approved, UL Listed, analog sensors and
bases. Each signaling line circuit can accommodate 99 sensor address points, using Address
numbers 01 to 99.
For a list of approved sensors and bases, refer to the
Compatibility Addendum to Gamewell-FCI
Manuals, P/N 9000-0427
.
3.5.1 Address Switches
Set the addresses using the rotary switches on each sensor or module. To set the address, turn each
of the two (2) rotary switches until the rotary switches point to the numbers indicating the proper
address (for example, SW1 @ #2 and SW2 @ #5 indicate Address #25).
3.5.2 Drift Compensation
The 7100 Series contains a program which performs continuous testing of analog sensors,
including sensitivity tests. This program will compensate all analog sensors for age and
environmental conditions. If a problem occurs in a sensor, a “Failed Test”, “Dirty” or “Very Dirty”
indication for the specific device will appear on the system display and will be recorded in the
Event Log and the Serial Port.
3.6 Addressable Modules
The 7100 Series accommodates only Gamewell-FCI approved, U.L. Listed, addressable monitor
and/or control modules. Each SLC can accommodate 98 addressable module points, using
Addresses 101 through 198.
For a list of approved modules, refer to the
Compatibility Addendum to Gamewell-FCI Manuals,
P/N 9000-0427
.
In the event of common mode noise problems, a Noise Control Module (NCM-1) may be installed.
(See Figure 3.4.1). The white wire lead must be connected to earth ground.
3.6.1 Address Switches
Set the addresses switches using the rotary switches on each module. To set the address, turn each
of the two (2) rotary switches until the rotary switches point to the numbers indicating the proper
address (for example, SW1 @ #5 and SW2 @ #7 indicate Address # 157).
NOTE:
The “100" digit is pre-set in all addressable modules.
!
WARNING: In systems incorporating the Positive Alarm Sequence (PAS) in conjunction with
addressable modules, (AMM-2F, -4F, -4SF), only one (1) initiating device may be connected to
each module (address). EXAMPLE: Connect only one manual station per an AMM-2F module.