RS-422-Main Port
Standard connector and cable when DMC-42x0 is ordered with RS-422 Option.
Pin #
Signal
1
RTS-
2
TXD-
3
RXD-
4
CTS-
5
GND
6
RTS+
7
TXD+
8
RXD+
9
CTS+
RS-422-Auxiliary Port
Standard connector and cable when DMC-42x0 is ordered with RS-422 Option.
Pin #
Signal
1
CTS-
2
RXD-
3
TXD-
4
RTS-
5
GND
6
CTS+
7
RXD+
8
TXD+
9
RTS+
RS-232/422 Configuration Jumpers
Location
Label
Function (If jumpered)
JP2 (-C012, default)
JP3 (-C022)
ARXD
Connects a 120 Ω Termination resistor between the differential “Receive”
inputs on the Aux Serial port. Pins 2 and 7 on RS-422 Auxiliary Port.
ACTS
Connects a 120 Ω Termination resistor between the differential “Clear To
Send” inputs on the Aux Serial port. Pins 1 and 6 on RS-422 Auxiliary Port.
JP2 (-C012, default)
JP2 (-C022)
MRXD
Connects a 120 Ω Termination resistor between the differential “Receive”
inputs on the Main Serial port. Pins 3 and 8 on RS-422 Main Port.
MCTS
Connects a 120 Ω
Termination resistor between the differential “Clear To
Send” inputs on the Main Serial port. Pins 4 and 9 on RS-422 Main Port.
JP2 (-CO12, default)
JP3 (-C022)
APWR
Do
not
use with RS-422 option.
Note:
The ARXD, ACTS, MRXD and MCTS should be installed for single-drop RS-422. For
multi-drop, the jumpers should be installed on the last device.
Appendices ▫ 171
DMC-42x0 User Manual
Summary of Contents for DMC-42 0 Series
Page 195: ...ICM 2900 PCB Layout Appendices 191 DMC 42x0 User Manual...
Page 205: ...CB 50 100 Drawings Appendices 201 DMC 42x0 User Manual...
Page 206: ...Appendices 202 DMC 42x0 User Manual...
Page 207: ...Appendices 203 DMC 42x0 User Manual...
Page 208: ...Appendices 204 DMC 42x0 User Manual...
Page 209: ...Appendices 205 DMC 42x0 User Manual...
Page 210: ...Appendices 206 DMC 42x0 User Manual...
Page 211: ...Appendices 207 DMC 42x0 User Manual...
Page 214: ...CB 50 80 Drawing Appendices 210 DMC 42x0 User Manual...