Fusion Installation & Commissioning Manual Approved document No UI-FBU-01 issue 3.0
84
TECHNICAL SPECIFICATION
General Specification.
Enclosure
Steel IP 30. Epoxy Powder coated Interpon Radon sil-
ver grey.
Dimensions. Std cabinet (FBUS)
340H x 460W x 120D mm
Weight 7.22 Kg (1 loop) 7.38 Kg (4 loop)
20mm knockouts 27 top, 6 rear , 2 bottom
Dimensions. Large cabinet (FBUL)
750H x 470W x 140D mm
Weight 17.54 Kg (8 loop)
20mm knockouts 28 top, 40 rear,2 bottom
Temperature range
-5 deg C to + 40 deg C max RH 95%
Number of fire zones (both cabinets)
16 (std) 32 or 64 (optional)
Max Number of loops
4 (FBUS) 8 (FBUL) Max 126 addressable points per
loop
Max conventional detection circuits
20 (FBUS) 36 (FBUL) Max 32 conventional detectors
per circuit.
Max loop current
500mA per loop
Detection protocol
Apollo: S90, XP95 & Discovery,
Apollo conventional series 65, Orbis +Twin Wire.
Hochiki conventional CDX range + Twin Wire.
Networking.
2 wire Comms, CAN 2.0 bus. Up to 16 panels / repeat-
ers. Max cable length 1KM fire resistant screened ca-
ble.
Printer
Optional panel printer (rs232) Not currently available.
PC connection
Download configuration only. Via USB – rs232 serial
conversion adapter SW-FSB25
Event log
100 Fire events ,100 fault events, 100 user events