FIRMWARE FLASH UPGRADE CONT’D
To reprogram a panel:- Continued
Repeat the procedure for each PCB in turn press CPU reset at the end of each session the diagnos-
tic LED on the PCB will flash when the card is operating following re– programming. Then press CPU
reset on the next PCB to be programmed and so on.
Panel will be programmed with latest software version, when finished, close down program and dis-
connect leads etc,
Restore the panel to normal operation by switching off the 'flashprog' switch.
Then it is necessary to restore factory defaults in the eeprom memory to prevent erroneous data
caused by any parameter changes that may have occurred .This is done by holding down button 2
on the panel keypad during a restart of the main display PCB .i.e press CPU reset whilst holding but-
ton 2. A menu will appear which allows you to select each board of the system in turn Make sure that
all boards fitted are initialized. Then re download the control panel from the back up file you made
before starting.
NOTE:-
occasionally the download software may be updated and if new parameters are needed an
import facility will be provided to enable conversion of existing panel parameters to any new require-
ments. Please check with supplier if in doubt.
During initialization you will be asked to confirm the number of boards (note for the board count and
FSB10 boards are not included in the count. The qty of remote panels will be reset to zero and any
power supply and device setting will be cleared.