Fusion Installation & Commissioning Manual Approved document No UI-FBU-01 issue 3.0
66
MENU AND CONTROL FUNCTIONS (Continued)
Engineering options (Cont)
This option requires the operator to input a security code
(1950)
in order to access all engineering
options. The ‘program mode switch’ must be in the
ON
position on the display board.
1.
Auto learn loop devices
. This facility is provided to enable an engineer to configure the
system with the minimum of effort. The entire contents of the loop are read in by the control
panel and placed in the memory for subsequent editing or downloading to the PC program.
Selecting this will re-learn all devices and remove any
existing settings
Use this option to modify an existing system if new devices have been added, removed or
modified. This option will not overwrite any existing settings.
Caution:-
Ensure any changed device settings are correct, i.e. input & output responses.
NOTE.
Before auto-learning takes place it is important that the placement of components and the
addressing of them on the loop, has been completed. Auto-learning can only take place once the
control panel has been initialised, if this option is selected during initialisation, a warning message is
displayed and auto-learn is halted until initialisation is completed. An option is provided either to learn
the complete loop and overwrite all the previous data or just learn new or removed devices without
affecting the rest of the programming. As a default all auto learned devices are placed in zone 1. The
device zone designations may be altered at the next step by selecting the edit loop devices option
2.
Connect to PC
. This is to allow access to the processor software for initial configuration of
the system, updates or modifications by a PC equipped with the correct configuration program.
For further details see the section on ‘PC Configuration’.
3.
Set Loop Parameters.
For details see the section on ’Panel Configuration’ .
Overwrite All Devices Found
Update New/Removed Devices Only