Fusion Installation & Commissioning Manual Approved document No UI-FBU-01 issue 3.0
75
CONFIGURATION (continued)
Device configuration
Group assignments:
1. Devices
Select individual devices and allocate them as inputs and/or outputs to the group
NOTE:- Ancillary bases must be set for the address before they are available as outputs in groups.
2.
Zones (not available in download program)
Quick set up utility to insert all addresses in a zone (only in the one loop) into a group as inputs and/
or outputs. Set the parameter as Add or Remove using scroll button. This option can also remove
devices from a group by zone.
NOTE:- This utility works as a ‘once off’ command and cannot be reviewed other than at device level.
Loop - Set programmable relays
There are four programmable relays available for each loop. The common sounder circuits 1 & 2,
which are monitored polarity reversal outputs and the common fire contact and remote signal
contact. These are clean changeover contacts. The remote signal contact has an LED associated
with the output on loop one and is intended for connection to remote signalling equipment.
Select the required relay using the scroll buttons
[2]
&
[8]
1. Sounder
1
2. Sounder
2
3. Sounder
3
4.
Sounder 4 (Note may be configured as remote signal output)
5.
Programmable relay 1
6.
Programmable relay 2
When selected:
Option 1:
Default assignments will set the relay to function with factory set defaults, which is
common operation.
Option 2:
Signals. NOTE: ( ) defines default setting. Responses can be defined for:
EVACUATE
(ON), Off or Pulse
COMMON FIRE
(ON), Off or Pulse
ALERT
On, Off or (PULSE)
PRECINCT
(ON), Off or Pulse
COMMON FAULT On, (OFF), or Pulse
SILENCE
(ON),
Off
Option 3:
Zones 1 - 16, On (continuous), Off or Pulsing for each zone
Option 4:
Zones 17 - 32
Option 5:
Zones 33 - 48
Option 6:
Zones 49 - 64
Option 7:
Groups 001 - 016, On, Off or Pulsing for each group
Option 8:
Groups 017 - 032
Etc….. Up to Group 150