Fusion Installation & Commissioning Manual Approved document No UI-FBU-01 issue 3.0
72
CONFIGURATION (continued)
Device configuration
Device types
TEM
(heat detector types)
These devices have only one associated text message & zone allocation. If the If the device is
Discovery protocol a sensitivity setting can apply. The default settings for this type are: - blank text,
unassigned for zone, sensitivity mid range , non silent mode, no group allocations, no base type set.
MAN
(manual call point types)
These devices have only one associated text message & zone allocation. The default settings for this
type are: - blank text, unassigned for zone, non silent mode, no group allocations.
SDR
(sounder / beacon types)
The sounder devices have only one associated text message & zone allocation. The default settings
for this type are: - blank text, unassigned for zone, no group allocations. Output attributes ‘Common’
‘Silenceable’ ‘Evac’ ‘Precinct’. Default volume setting [4]. Non Auto shutdown.
Part Number
Type
Sensitivity
Input
attribute
55000-400
XP95 Heat detector
n/a
[s]
55000-401
XP95 High heat detector
n/a
[s]
58000-400 Discovery
heat
detector 1-5
[s]
Part Number
Type
Sensitivity
Input
attribute
55000-908
XP95 Man call point
n/a
[s]
58000-908
Discovery Man call pt
n/a
[s]
Part Number
Type
Output
attributes
45681-276
XP95 ancillary sounder base
S,E,P
45681-277
XP95 base sounder
S,E,P
45681-331
XP95 bounder beacon base
S,E,P
45681-335 XP95
beacon
S,E,P
55000-001
XP95 open area sounder beacon
S,E,P
55000-009/877
XP95 beacon
S,E,P
55000-278/291 XP95
sounder
S,E,P
55000-852
XP95 sounder controller
S,E,P