Fusion Installation & Commissioning Manual Approved document No UI-FBU-01 issue 3.0
76
CONFIGURATION (continued)
Loop - Set default sounder response
This option informs sounders and loop sounders how to react when not in the active fire group. The
choice is Pulsing or Off.
Loop - Set responses to remote panels
This effectively programs the network interaction between control panels. Each loop must be set up
according to requirements.
The signals available from each panel, 00 - 16 are:-
EVACUATE, 2ND ALARM, 1ST ALARM, ALERT, PRECINCT, FAULT.
The responses can be set for each of the following outputs:
Loop Sounders (en bloc)
Off, Continuous, Pulsing
Common Sounder 1
Off, Continuous, Pulsing
Common Sounder 2
Off, Continuous, Pulsing
Common Sounder 3
Off, Continuous, Pulsing
Common Sounder 4
Off, Continuous, Pulsing
Loop Modules (RIO) (en bloc)
Off, Continuous, Pulsing
Remote Signal Output
Off, Continuous, Pulsing
The settings should be checked for every loop on all panels in a network.
PLEASE NOTE:- With many options available it is possible to select conflicting requirements
which affect one output. Take care with assignments.