PC CONFIGURATION (Continued)
Before creating or editing a configuration file it is important to understand the available options and
the program/system limitations. The following paragraphs describe the basic functions of the program
and how they affect the system operation when downloaded to the on board micro-processor.
The programmer should also be in possession of the device information, i.e. address, type, location,
etc., and understand the specified operation. The available device types and their function are
described in the configuration section earlier in this manual, but are outlined again here for
clarification.
The device types are:-
Sensors; i.e. Ionisation (ION), Optical (OPT) and Temperature (TEM)
Manual Call Point (MAN)
Sounder module / Addressable sounder / Beacon (SDR)
Input/output module (RIO)
Zone Monitor (ZMU)
NOTE .
The device type assigned to each address must match the installed device type.
Assigning devices to zones.
Devices which are to be indicated zonally by the panel, i.e. sensors, call points, zone modules and
input modules must be assigned to a zone in the range 1 to 64. SDR device types (sounders) can be
assigned to a zone in the range 1 to 64. Sounders assigned to a specific zone operate according to
output response settings. All other sounders are either silent or pulsed, depending on the 'default
ringing mode' which is selected in the edit screen.
Input/output modules (RIO) can be assigned to a zone in the range 1 to 64
I/O modules assigned to a specific zone turn their output on according to output response settings.