Fusion Installation & Commissioning Manual Approved document No UI-FBU-01 issue 3.0
46
COMMISSIONING (Cont’d)
Analogue Addressable Field devices
The control panel operates with the Apollo XP95 & Discovery protocols and accepts the full range of
field devices. Field devices should be connected to the loop circuit in accordance with the
instructions supplied with them ensuring that, where necessary, a 24V DC supply is available and
monitoring resistors are fitted.
Device address
Each device on the system (excluding short circuit isolators) must have a unique address.
Apollo detectors are addressed by means of the 'XPERT address card' which is either supplied blank
for on-site configuration, or pre-configured to simply slot into the appropriate device.
The standard address range for Apollo devices is 1 - 126. Please refer to Apollo device instructions
for further information.
Devices do not have to be addressed in the order in which they are wired. An error message will
appear on the LCD display to indicate any duplicated addresses.
The chart on the following page is a brief overview of the supported devices and relevant type codes.
Part numbers are correct at time of publication. For further devices not listed, please contact our