Mechanically Installing the Supervised IAM 

 

Install the Supervised IAM into a UL Listed single-gang, 4-inch square, or 4-inch octagonal electrical box 
(not supplied) using Figure 4 as a reference.  Mount the Supervised IAM to the electrical box as follows: 

 

1.  Insert the Supervised IAM into the electrical box; the attached field wiring holds the Supervised IAM 

in place inside the electrical box. 

2.  Secure the cover to the back box using the two #6/32 flathead screws. 
 

 

 

Note:

  Simplex offers semi-flush and surface covers (ordered separately) with a light pipe.  The cover(s) 

with light pipe allow viewing of the communications LED without taking the cover off.  Installation 
of the 4090-9806 semi-flush cover and 4090-9807 surface cover are detailed in publication 

4090 

IDNet

 Semi-Flush/Surface Covers and IAM Bracket Installation Instruction (574-796).

 

 

Figure 4.  Supervised IAM Back Box Installation 

4090-9001 Supervised IAM

Installation Instructions

 

574-331 

Rev. E 

574-331 

Rev. E 

 2000 Simplex Time Recorder Co., Westminster, MA 01441-0001

 

All specifications and other information shown were current as of publication, and are subject to change without notice. 
IDNet

 is a trademark of the Simplex Time Recorder Company. 

MAPNET II

 Communication Net is protected by U.S. Patent No.4,796,025. 

UL Listed 

Single-Gang 

Electrical Box 

(Not Supplied) 

Cover 

(Not Supplied)

 

Field Wiring

 

4090-9001 

Supervised IAM 

Assembly 

#6/32 Flathead Screw 

(Not Supplied)

 

 

Cautions and Warnings 

 

DO NOT INSTALL ANY SIMPLEX PRODUCT THAT APPEARS DAMAGED.

  

Upon unpacking 

your Simplex product, inspect the contents of the carton for shipping damage.  If damage is apparent, 
immediately file a claim with the carrier and notify Simplex. 

 

ELECTRICAL HAZARD -

 

Disconnect electrical power when making any internal adjustments or repairs.  

Servicing should be performed by qualified Simplex Representatives.

 

 

STATIC HAZARD -

 

Static electricity can damage components.  Ground yourself before opening or 

installing components. 

 

 

Introduction 

 

IDNet

 

The 4090-9001 Supervised Individual Addressable Module (IAM) provide four-state status information 
(NORMAL, OPEN, CURRENT-LIMITED, and SHORT) to the 4010 Fire Alarm Control Panel (FACP) 
via the IDNet

 channel.  The IDNet channel provides the communication link between Supervised IAM 

and 4010 FACP and powers the entire IAM circuitry.  A typical application for this module would be to 
monitor a waterflow switch. 

 

MAPNET II

 

 

The 4090-9001 Supervised IAM provides three-state status information (NORMAL, OPEN, and ALARM) 
to the host FACP via the MAPNET II channel.  Applications that require current limit sensing are not 
compatible with MAPNET II channels (Tamper/Waterflow on the same IAM, Manual release/abort, etc.).  
The MAPNET II channel provides the communication link between the Supervised IAM and host 4100, or 
4120, or 4020 FACP and powers the entire IAM circuitry. 

 

 

Installation 

 

Supervised IAM installation consists of the following: 

 

• 

Setting the Supervised IAMs address 

• 

Making electrical connections to the Supervised IAM 

• 

Mechanically installing the Supervised IAM 

 

Front View

Rear View

 

 

Label 

DIP Switch 

(Under Re-sealable Label)

 

LED 

Terminal 

Note:

  The LED flashes approximately once every three seconds to indicate valid 

communications with the FACP. 

 

Figure 1.  Supervised IAM Installation 

firealarmresources.com

Reviews: