1-2. Heating operation
A sensor (room temperature thermistor) built in indoor unit body will usually perceive difference or
variation between setting temperature and present room temperature, and controls operation rota-
tion number of compressor.
• If the room temperature is 6.0 °C lower than a set temperature, the operation rotation number of
compressor will attain to maximum performance.
• If the room temperature is 1.0 °C higher than a set temperature, the compressor will be stopped.
• When the room temperature is within the range of +1.0°C to -6.0°C of the setting temperature, the
rotation number of compressor is controlled within the range shown below.
•
Rotation number range of compressor
Unit: rps
Model name
Minimum rotation number
Maximum rotation number
ASHG07KPCE
ASHG09KPCE
ASHG12KPCE
10
114
•
Limit of maximum speed based on outdoor temperature
In heating operation, maximum rotation number is defined by outdoor temperature and fan mode.
A zone
17°C
B zone
19°C
C zone
14°C
12°C
Outdoor
temperature rises
Outdoor
temperature drops
Unit: rps
Model name
Outdoor
temperature zone
Indoor unit fan mode
HIGH
MED
LOW
QUIET
ASHG07KPCE
ASHG09KPCE
A zone
114
114
110
90
B zone
114
114
96
84
C zone
110
110
84
52
ASHG12KPCE
A zone
114
114
78
78
B zone
114
114
78
73
C zone
110
110
73
46
1-2. Heating operation
- (04-3) -
1. Rotation number control of compressor
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS
Summary of Contents for General ASHG07KPCE
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2021 12 16 SR_CH01_AS059EG_01 ...
Page 13: ...2 TECHNICAL DATA AND PARTS LIST 2022 07 07 SR_CH02_AS059EG_02 ...
Page 31: ...3 TROUBLESHOOTING 2022 07 07 SR_CH03_AS059EG_02 ...
Page 34: ......
Page 92: ...6 2 Outdoor unit 03 58 6 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Page 93: ...4 CONTROL AND FUNCTIONS 2022 07 07 SR_CH04_AS059EG_02 ...
Page 125: ...5 FILED WORKING 2022 07 07 SR_CH05_AS059EG_02 ...