2-6. E: 42. Indoor unit heat exchanger sensor error (Indoor unit)
Indicator
Indoor unit
Operation indicator
4 time flash
Timer indicator
2 time flash
Economy indicator
Continuous flash
Error code
E: 42
Detective actuator
Indoor unit main PCB
When heat exchanger temperature thermistor open or
short circuit is detected.
Heat exchanger temperature
thermistor
Forecast of cause
Connector connection failure
Thermistor failure
Main PCB failure
Check point 1. Check connection of connector
•
Check if connector is loose or removed.
•
Check erroneous connection.
•
Check if thermistor cable is open
-> Reset power when reinstalling due to removed connector or incorrect wiring.
↓
Check point 2. Remove connector and check thermistor resistance value
•
For the heat exchanger thermistor resistance value, refer to
•
If thermistor is either open or shorted, replace it and reset the power.
↓
Check point 3. Check voltage of main PCB
Make sure circuit diagram of each indoor unit and check terminal voltage at thermis-
tor (DC 5.0 V).
NOTE:
For details of thermistor connector, refer to
TECHNICAL DATA AND PARTS LIST on page 02-13.
(07-12 models: CN1)
If the voltage does not appear, replace main PCB.
↓
End
2-6. E: 42. Indoor unit heat exchanger sensor error (Indoor unit)
- (03-11) -
2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING
Summary of Contents for General ASHG07KPCE
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2021 12 16 SR_CH01_AS059EG_01 ...
Page 13: ...2 TECHNICAL DATA AND PARTS LIST 2022 07 07 SR_CH02_AS059EG_02 ...
Page 31: ...3 TROUBLESHOOTING 2022 07 07 SR_CH03_AS059EG_02 ...
Page 34: ......
Page 92: ...6 2 Outdoor unit 03 58 6 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Page 93: ...4 CONTROL AND FUNCTIONS 2022 07 07 SR_CH04_AS059EG_02 ...
Page 125: ...5 FILED WORKING 2022 07 07 SR_CH05_AS059EG_02 ...