2-7. E: 51. Indoor unit fan motor error (Indoor unit)
Indicator
Indoor unit
Operation indicator
5 time flash
Timer indicator
1 time flash
Economy indicator
Continuous flash
Error code
E: 51
Detective actuator
Indoor unit
main PCB
When the actual rotation number of the indoor unit fan
motor is below 1/3 of the target rotation number
continuously for more than 56 seconds.
Fan motor
Forecast of cause
Fan rotation failure
Fan motor winding open
Motor protection by surrounding temperature rise
Control PCB failure
Indoor unit fan motor failure
Check point 1. Check rotation of fan
Rotate the fan by hand when operation is off. (Check if fan is caught, dropped off or locked motor)
→ If fan or bearing is abnormal, replace it.
↓
Check point 2. Check ambient temperature around motor
Check excessively high temperature around the motor. (If there is any surrounding equipment that
causes heat)
→ Upon the temperature coming down, restart operation.
↓
Check point 3. Check indoor unit fan motor
Check Indoor unit fan motor. (Refer to indoor unit fan motor in
03-48.)
→ If Indoor unit fan motor is abnormal, replace Indoor unit fan motor.
↓
Check point 4. Replace the main PCB
If Check Point 1 to 3 do not improve the symptom, replace the main PCB.
↓
End
2-7. E: 51. Indoor unit fan motor error (Indoor unit)
- (03-12) -
2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING
Summary of Contents for General ASHG07KPCE
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2021 12 16 SR_CH01_AS059EG_01 ...
Page 13: ...2 TECHNICAL DATA AND PARTS LIST 2022 07 07 SR_CH02_AS059EG_02 ...
Page 31: ...3 TROUBLESHOOTING 2022 07 07 SR_CH03_AS059EG_02 ...
Page 34: ......
Page 92: ...6 2 Outdoor unit 03 58 6 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Page 93: ...4 CONTROL AND FUNCTIONS 2022 07 07 SR_CH04_AS059EG_02 ...
Page 125: ...5 FILED WORKING 2022 07 07 SR_CH05_AS059EG_02 ...